| 2018-05-13 11:43:40 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. FBC EC C502.1, NO INFORMATION PROVIDED. AS THIS IS |
| | AN INCREASE IN CONDITIONED SPACE, THIS IS CONSIDERED AN |
| | ADDITION IN ADDITION TO A LEVEL 2 ALTERATION (FBC EB), |
| | PLEASE REVISE GENERAL NOTES A1. |
| | |
| | 2. FBC B 1609, SPECIFY COMPONENT AND CLADDING DESIGN |
| | PRESSURES AND INCLUDE WIND DESIGN CRITERIA (170 MPH |
| | EXPOSURE D MINIMUM). |
| | |
| | 3. ON THE SLIDING GLASS DOOR PRODUCT APPROVAL, INDICATE |
| | OPTIONS ELECTED TO SHOW COMPLIANCE WITH THE DESIGN |
| | PRESSURE REQUIREMENTS. |
| | |
| | 4. REVISE PLAN TO INCLUDE TYPE OF FLOORING PROPOSED, |
| | FBC 107. |
| | |
| | IF A FLOORING UNDERLAYMENT IS PROPOSED (FOR TILE OR |
| | OTHER RESILIENT FLOORING), ADVISE AS TO UNDERLAYMENT |
| | PROPOSED. THREE TEST REPORTS ARE REQUIRED. |
| | |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| | CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | |
| | 5. FBC 107, REVISE PLAN TO INCLUDE UNDER AIR |
| | CALCULATIONS: |
| | EXISTING SQUARE FOOT UNDER AIR |
| | PROPOSED NEW UNDER AIR |
| | NEW TOTAL |
| | |
| | |
| | |
| | |