| 2018-04-18 11:39:36 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE ENGINEER'S PLANS REFERENCE THE FBC FIFTH EDITION |
| | (2014). THE FBC SIXTH EDITION (2017) WENT INTO EFFECT |
| | ON JANUARY 1, 2018. ALL NEW PERMITS APPLIED FOR ON OR |
| | AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND |
| | REFERENCE THE FBC SIXTH EDITION (2017). FS CHAPTER 553 |
| | |
| | 2) THE WIND DESIGN DATA IS NOT SPECIFIED ON THE |
| | ENGINEER'S DRAWINGS. FBC EXISTING BUILDING SECTION |
| | 606.1 |
| | |
| | 3) THE ENGINEER SHALL SPECIFY THE REQUIRED DESIGN |
| | UPLIFT , GRAVITY AND LATERAL LOADS FOR THE NEW |
| | STRUCTURAL BEAMS ON THE SIGNED AND SEALED PLANS. THE |
| | EXISTING CONNECTORS WILL HAVE TO BE EVALUATED BY THE |
| | ENGINEER TO DETERMINE IF THEY ARE ADEQUATE OR NEED TO |
| | BE REPLACED. SPECIFY ANY NEW CONNECTORS ON THE PLANS. |
| | FBC EXISTING BUILDING SECTION 606.1 |
| | |
| | 4) LIMITATION NUMBER 7 ON PAGE 16 OF THE ROOFING |
| | PRODUCT ( NOA NO. 13-0204.14 ) REQUIRES THE RAS 117 |
| | CALCULATIONS TO BE SIGNED AND SEALED. FAC 61G15-23.001 |
| | REQUIRES A FLORIDA LICENSED PROFESSIONAL ENGINEER TO |
| | SIGN AND SEAL ALL OF THEIR DOCUMENTS THAT ARE SUBMITTED |
| | FOR PUBLIC RECORD. FS 471.025 |
| | |
| | 5) THE PLANS INDICATE THAT THE EXISTING GAS WATER |
| | HEATER IS TO BE MOVED TO THE EXTERIOR OF THE STRUCTURE. |
| | PROVIDE ADDITIONAL INFORMATION SUCH AS IS IT A TANKLESS |
| | WATER HEATER LABELED FOR OUTDOOR INSTALLATION OR ONE |
| | WITH A TANK THAT REQUIRES IT TO BE INSIDE OF A |
| | STRUCTURE. IF A STRUCTURE IS REQUIRED TO PROTECT IT |
| | FROM THE ELEMENTS PROVIDE DETAILS. FBC 107.2.1 AND |
| | FBCR-P2801.3 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |