2018-04-20 06:39:38ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. "1 SET OF 3# 4/0 IN 3" RMC FROM METER TO CONTROLLER"
 DOES NOT MEET THE REQUIREMENTS OF NEC 250.24(C). THE
 GROUNDED CONDUCTOR MUST BE BROUGHT TO THE SERVICE
 DISCONNECTING MEANS (FIRE PUMP CONTROLLER).
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN
 REVIEW COMMENTS. WHEN RESUBMITTING, IT IS HELPFUL TO
 PROVIDE A RESPONSE LETTER ADDRESSING
 EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO
 THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  