| 2018-04-26 13:01:26 | MOVED COMMENTS TO 18040627 |
| | |
| | |
| 2018-04-23 06:47:55 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND |
| | SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE |
| | ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H); |
| | 471.025; FBC 107.2.1, 107.3.5 |
| | |
| | 2. PROVIDE CLARIFICATION OF WHAT LIGHTS AND RECEPTACLES |
| | ARE BEING REPLACED IN WHAT BUILDINGS ON THE PLANS |
| | SUBMITTED FOR REVIEW. |
| | |
| | 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE |
| | CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE |
| | TO COMPLY WITH CODE. NEC 210.8, 210.12, |
| | 215.5, 408.4; FBC RE3706.2, RE3902 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN |
| | REVIEW COMMENTS. WHEN RESUBMITTING, IT IS HELPFUL TO |
| | PROVIDE A RESPONSE LETTER ADDRESSING |
| | EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO |
| | THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 6TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 6TH |
| | EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 6TH EDITION, PART |
| | VIII ELECTRICAL |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |