Plan Review Notes
Plan Review Notes For Permit 18040628
Permit Number 18040628
Review Stop E
Sequence Number 1
Notes
Date Text
2018-04-26 13:01:26MOVED COMMENTS TO 18040627
  
  
2018-04-23 06:47:55ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; FBC 107.2.1, 107.3.5
  
 2. PROVIDE CLARIFICATION OF WHAT LIGHTS AND RECEPTACLES
 ARE BEING REPLACED IN WHAT BUILDINGS ON THE PLANS
 SUBMITTED FOR REVIEW.
  
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12,
 215.5, 408.4; FBC RE3706.2, RE3902
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN
 REVIEW COMMENTS. WHEN RESUBMITTING, IT IS HELPFUL TO
 PROVIDE A RESPONSE LETTER ADDRESSING
 EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO
 THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 6TH
 EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 6TH EDITION, PART
 VIII ELECTRICAL
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 [email protected]
 561-657-1653
  