| 2018-04-26 08:24:54 | 4/26/18 DENIED BY PLUMBING | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | 1. THE REVISION THAT WAS SUBMITTED IS NOT CLEAR TO WHAT | | | IT IS FOR. IT SAID WATER HEATER REV. ON A REQUEST FORM | | | BUT WILL NEED SOME TYPE OF NARRATIVE DESCRIPTION ON | | | WHAT THIS SUBMITTAL OF PAGE P0.0.00B, I CAN NOT TELL IF | | | IT IS MISSING PAGE OR YOUR ADDING THIS ONE. THERE IS A | | | P 1.3.00B, P3.0.00B AND P3.1.00B PLEASE CERTIFY OR GIVE | | | DIRECTION TO WHAT YOU NEED TO BE DONE, I CALLED MR. | | | VINCE VECCHARELLA TO TRY TO GET DIRECTION AND LEFT A | | | MESSAGE WITHOUT NO RESPONSE. | | | | | | 2. ARE THERE TWO WATER HEATERS BEING INSTALLED AND DOES | | | ELECTRICAL NEED TO REVIEW THIS AS WELL BECAUSE ON YOU | | | P.3.0.00B DOES NOT SHOW TWO BEING IN PLACE. | | | | | | PLEASE FEEL FREE TO CONTACT ME DIRECT. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | [email protected] | | | 561-805-6720 | | | |
|