| 2018-04-24 17:14:05 | 04/24/18 MET WITH SAM. HE SAID HE DIDN'T SEE THE REVIEW | | | COMMENTS. THEREFORE, COMMENTS FROM FIRST REVIEW STILL | | | APPLIES. | | | | | | | | | RESIDENTIAL (R3) REVISION, SECOND MECHANICAL REVIEW | | | CHECKLIST. COMMENTS | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1-PLANS NEED TO BE REVISED AND SIGNED AND SEALED BY THE | | | MECHANICAL ENGINEER OF RECORD AS REQUIRED BY CHAPTER | | | 471 F.S.. | | | | | | 2- EQUIPMENT SEER AND MANUFACTURER'S MODEL WAS CHANGED. | | | NEED TO REVISE THE ENERGY CALCULATIONS TO REFLECT THE | | | NEW EQUIPMENT SEER. SEC. R103.4 FBC-ENERGY | | | CONSERVATION. | | | | | | 3- REVISED PLAN IS MISSING THE EXHAUST FAN IN BATHROOM | | | LOCATED BETWEEN BEDROOM #2 AND BEDROOM #3. REVISE AS | | | REQUIRED. ORIGINAL APPROVED PLAN PLAN HAD THIS EXHAUST | | | FAN SHOWN. SEC. R303.3 FBC-RESIDENTIAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | |
|