2018-04-24 17:14:0504/24/18 MET WITH SAM. HE SAID HE DIDN'T SEE THE REVIEW
 COMMENTS. THEREFORE, COMMENTS FROM FIRST REVIEW STILL
 APPLIES.
  
  
 RESIDENTIAL (R3) REVISION, SECOND MECHANICAL REVIEW
 CHECKLIST. COMMENTS
 CODE: FBC 5TH EDITION (2014).
  
 1-PLANS NEED TO BE REVISED AND SIGNED AND SEALED BY THE
 MECHANICAL ENGINEER OF RECORD AS REQUIRED BY CHAPTER
 471 F.S..
  
 2- EQUIPMENT SEER AND MANUFACTURER'S MODEL WAS CHANGED.
 NEED TO REVISE THE ENERGY CALCULATIONS TO REFLECT THE
 NEW EQUIPMENT SEER. SEC. R103.4 FBC-ENERGY
 CONSERVATION.
  
 3- REVISED PLAN IS MISSING THE EXHAUST FAN IN BATHROOM
 LOCATED BETWEEN BEDROOM #2 AND BEDROOM #3. REVISE AS
 REQUIRED. ORIGINAL APPROVED PLAN PLAN HAD THIS EXHAUST
 FAN SHOWN. SEC. R303.3 FBC-RESIDENTIAL.
  