| Plan Review Notes For Permit 18040540 |
| Permit Number |
18040540 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-04-16 10:41:30 | BUILDING PROVISO | | | | | | PROVIDE TYPE OF FLOORING TO BE INSTALLED ALONG WITH THE | | | SOUND PROOFING SPECIFICATIONS. | | | | | | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: | | | | | | 1A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | 1C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | | | 1D) FLAME SPREAD INDEX. A COMPARATIVE MEASURE, | | | EXPRESSED AS A DIMENSIONLESS NUMBER, DERIVED FROM | | | VISUAL MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME | | | FOR A MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR | | | UL 723. | | | |
|