2018-04-18 17:57:38BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- SHEET G1.0 LIFESAFETY PLAN:
 A) PLAN SUBMITTED IS NOT DRAWN TO THE SCALE
 3/16"=1'-0". PROVIDE PLAN THAT MATCHES SPECIFIED SCALE.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 B) PROPOSED EGRESS DOOR IS PASSING THROUGH THE BREAK
 ROOM. AN EXIT ACCESS SHALL NOT PASS THROUGH A ROOM THAT
 CAN BE LOCKED TO PREVENT EGRESS. PROVIDE SPECIFICATIONS
 SHOWING COMPLIANCE WITH SEC. 1016.2(3) FBC.
  
 C) TRAVEL DISTANCE NEEDS TO BE TAKEN FROM THE MOST
 REMOTE POINT TO THE ENTRANCE TO THE "EXIT" AS REQUIRED
 BY SEC. 1017.3 FBC. REVISE PLAN AS REQUIRED AND
 INFORMATION SHOWN UNDER NUMBER AND ARRANGEMENT OF EXITS
 ON SAME SHEET. NOTE: SEE DEFINITION OF "EXIT".
  
 D) PLAN NOT DRAWN TO SCALE. IT LOOKS LIKE THE DEAD END
 CORRIDOR DOESN'T COMPLY WITH SEC. 1020.4 FBC. IT LOOKS
 LIKE IT'S MORE THAN 50'. NOTE: THE END CORRIDOR NEEDS
 TO BE DIMENSIONED TO THE WALL. REVISE AS REQUIRED.
  
 E) THE CLEAR EGRESS WIDTH SPECIFIED ON THE PLAN FOR THE
 DOORS IS NOT CORRECT. 36" DOOR DOESN'T PROVIDE 36"
 CLEAR OPENING AND (2)36" DOORS DON'T PROVIDE 72" CLEAR
 EGRESS WIDTH. SEE SEC. 1010.1.1 FBC AND REVISE AS
 REQUIRED.
  
 F) PLAN NOT DRAWN TO SCALE. SHOW ON PLAN HOW THE
 DISTANCE BETWEEN THE EXIT DOORS WAS TAKEN TO COMPLY
 WITH SEC. 1007.1 FBC.
  
 G) THE DEMISING FIRE RATED PARTITION IS CREATING TWO
 DIFFERENT TENANTS. PROVIDE COMPLETE INFORMATION SHOWING
 COMPLIANCE WITH THE EXIT ACCESS FOR THE TENANT WITH ONE
 EGRESS DOOR AS REQUIRED BY SEC. 1016.2.1 FBC.
  
 H) NUMBER AND ARRANGEMENT OF EXITS INFORMATION IS NOT
 CLEAR. IT SAYS THAT 2 DOORS ARE REQUIRED AND THAT 2
 DOORS ARE PROVIDED. PLANS SHOW 3 DOORS. COORDINATE
 INFORMATION WITH PLANS. SEC.107.2.1 CITY AMENDMENTS.
  
 I) LIFESAFETY PLAN IS MISSING THE EXIT SIGNS AND FIRE
 EXTINGUISHER ON THE PLAN. SEC. 1001.4 FBC. SEC. 107.2.1
 CITY AMENDMENTS.
  
 J) THE LEVEL EGRESS WIDTH OF 144 INCHES SHOWN UNDER
 CODE SUMMARY IS INCORRECT. REVISE AS REQUIRED.
 COORDINATE WITH ITEM #1E ABOVE. SEC. 1010.1.1 FBC.
  
 2- SHEET A-2.0:
 A) NEW DEMISING PARTITION HATCHING SHOWN ON FLOOR PLAN
 DOESN'T MATCH THE FIRE RATED LEGEND SHOWN ON SAME
 SHEET. REVISE AS REQUIRED TO MATCH TO AVOID CONFLICTS.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 B) COORDINATE WALL TYPES SHOWN ON FLOOR PLAN WITH WALL
 TYPES SHOWN ON SHEET A-4.0. CLEARLY IDENTIFY THE FIRE
 RATED WALLS. SEC. 107.2.1 CITY AMENDMENTS.
  
 C) REVISE DETAIL 4/A-4: PROVIDE DETAIL AND
 SPECIFICATIONS FOR WALL CONNECTION DETAIL IN FIRE RATED
 WALL ASSEMBLY. SEC. 701.1 FBC.
  
 D) IT LOOKS LIKE THERE MAY BE NOT ENOUGH ROOM TO
 INSTALL THE PROPOSED EGRESS DOOR AND COMPLY WITH THE
 MIN. 18" MANEUVERING CLEARANCE OF SEC. 404.2.4
 FBC-ACCESSIBILITY. PROVIDE ACTUAL CORRIDOR DIMENSION
 AND COMPLETE DETAIL/SPECIFICATIONS ON THE HINGED JAMB
 SIDE OF THE PROPOSED DOOR. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 3- REVISE DOOR JAMB/HEAD DETAILS. WOOD BACKING OR
 BLOCKING NEEDS TO BE FIRE RESISTANT TREATED WOOD.
 PROVIDE SPECIFICATIONS. SEC. 603 FBC.
  
 4- THERE ARE TWO TENANT SPACES CREATED WITH THE
 PROPOSED DEMISING WALL. A SEPARATE PERMIT IS REQUIRED
 FOR EACH TENANT SPACE FOR PROPER INSPECTIONS AND
 RECORDS MANAGEMENT. SEC. 105.1 AND SEC. 107.2.1.4 CITY
 AMENDMENTS. NOTE: THERE IS NO ADDITIONAL FEES FOR THE
 SEPARATE PERMIT APPLICATIONS. PLEASE COORDINATE WITH
 MIKE ORIO ( SEE CONTACT INFORMATION BELOW) FOR PROPER
 ADDRESSING OF EACH TENANT.
  
 MICHAEL P ORIO
 GIS SUPPORT SPECIALIST
 INFORMATION TECHNOLOGY
  
 PHONE: 494-1040 EXT: 1080
 FAX: 494-1117
 E-MAIL: [email protected]
  
 -NOTE:
 PLANS SUBMITTED DON'T SHOW THE ENCLOSED ELEVATOR LOBBY.
 THIS BUILDING WAS ORIGINALLY DESIGNED WITH ENCLOSED
 ELEVATOR LOBBY. COORDINATE WITH PERMIT #17080045 FOR
 THE RECONSTRUCTION OF ELEVATOR LOBBY.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
  