| 2018-04-18 17:57:38 | BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017). |
| | |
| | 1- SHEET G1.0 LIFESAFETY PLAN: |
| | A) PLAN SUBMITTED IS NOT DRAWN TO THE SCALE |
| | 3/16"=1'-0". PROVIDE PLAN THAT MATCHES SPECIFIED SCALE. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | B) PROPOSED EGRESS DOOR IS PASSING THROUGH THE BREAK |
| | ROOM. AN EXIT ACCESS SHALL NOT PASS THROUGH A ROOM THAT |
| | CAN BE LOCKED TO PREVENT EGRESS. PROVIDE SPECIFICATIONS |
| | SHOWING COMPLIANCE WITH SEC. 1016.2(3) FBC. |
| | |
| | C) TRAVEL DISTANCE NEEDS TO BE TAKEN FROM THE MOST |
| | REMOTE POINT TO THE ENTRANCE TO THE "EXIT" AS REQUIRED |
| | BY SEC. 1017.3 FBC. REVISE PLAN AS REQUIRED AND |
| | INFORMATION SHOWN UNDER NUMBER AND ARRANGEMENT OF EXITS |
| | ON SAME SHEET. NOTE: SEE DEFINITION OF "EXIT". |
| | |
| | D) PLAN NOT DRAWN TO SCALE. IT LOOKS LIKE THE DEAD END |
| | CORRIDOR DOESN'T COMPLY WITH SEC. 1020.4 FBC. IT LOOKS |
| | LIKE IT'S MORE THAN 50'. NOTE: THE END CORRIDOR NEEDS |
| | TO BE DIMENSIONED TO THE WALL. REVISE AS REQUIRED. |
| | |
| | E) THE CLEAR EGRESS WIDTH SPECIFIED ON THE PLAN FOR THE |
| | DOORS IS NOT CORRECT. 36" DOOR DOESN'T PROVIDE 36" |
| | CLEAR OPENING AND (2)36" DOORS DON'T PROVIDE 72" CLEAR |
| | EGRESS WIDTH. SEE SEC. 1010.1.1 FBC AND REVISE AS |
| | REQUIRED. |
| | |
| | F) PLAN NOT DRAWN TO SCALE. SHOW ON PLAN HOW THE |
| | DISTANCE BETWEEN THE EXIT DOORS WAS TAKEN TO COMPLY |
| | WITH SEC. 1007.1 FBC. |
| | |
| | G) THE DEMISING FIRE RATED PARTITION IS CREATING TWO |
| | DIFFERENT TENANTS. PROVIDE COMPLETE INFORMATION SHOWING |
| | COMPLIANCE WITH THE EXIT ACCESS FOR THE TENANT WITH ONE |
| | EGRESS DOOR AS REQUIRED BY SEC. 1016.2.1 FBC. |
| | |
| | H) NUMBER AND ARRANGEMENT OF EXITS INFORMATION IS NOT |
| | CLEAR. IT SAYS THAT 2 DOORS ARE REQUIRED AND THAT 2 |
| | DOORS ARE PROVIDED. PLANS SHOW 3 DOORS. COORDINATE |
| | INFORMATION WITH PLANS. SEC.107.2.1 CITY AMENDMENTS. |
| | |
| | I) LIFESAFETY PLAN IS MISSING THE EXIT SIGNS AND FIRE |
| | EXTINGUISHER ON THE PLAN. SEC. 1001.4 FBC. SEC. 107.2.1 |
| | CITY AMENDMENTS. |
| | |
| | J) THE LEVEL EGRESS WIDTH OF 144 INCHES SHOWN UNDER |
| | CODE SUMMARY IS INCORRECT. REVISE AS REQUIRED. |
| | COORDINATE WITH ITEM #1E ABOVE. SEC. 1010.1.1 FBC. |
| | |
| | 2- SHEET A-2.0: |
| | A) NEW DEMISING PARTITION HATCHING SHOWN ON FLOOR PLAN |
| | DOESN'T MATCH THE FIRE RATED LEGEND SHOWN ON SAME |
| | SHEET. REVISE AS REQUIRED TO MATCH TO AVOID CONFLICTS. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | B) COORDINATE WALL TYPES SHOWN ON FLOOR PLAN WITH WALL |
| | TYPES SHOWN ON SHEET A-4.0. CLEARLY IDENTIFY THE FIRE |
| | RATED WALLS. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | C) REVISE DETAIL 4/A-4: PROVIDE DETAIL AND |
| | SPECIFICATIONS FOR WALL CONNECTION DETAIL IN FIRE RATED |
| | WALL ASSEMBLY. SEC. 701.1 FBC. |
| | |
| | D) IT LOOKS LIKE THERE MAY BE NOT ENOUGH ROOM TO |
| | INSTALL THE PROPOSED EGRESS DOOR AND COMPLY WITH THE |
| | MIN. 18" MANEUVERING CLEARANCE OF SEC. 404.2.4 |
| | FBC-ACCESSIBILITY. PROVIDE ACTUAL CORRIDOR DIMENSION |
| | AND COMPLETE DETAIL/SPECIFICATIONS ON THE HINGED JAMB |
| | SIDE OF THE PROPOSED DOOR. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 3- REVISE DOOR JAMB/HEAD DETAILS. WOOD BACKING OR |
| | BLOCKING NEEDS TO BE FIRE RESISTANT TREATED WOOD. |
| | PROVIDE SPECIFICATIONS. SEC. 603 FBC. |
| | |
| | 4- THERE ARE TWO TENANT SPACES CREATED WITH THE |
| | PROPOSED DEMISING WALL. A SEPARATE PERMIT IS REQUIRED |
| | FOR EACH TENANT SPACE FOR PROPER INSPECTIONS AND |
| | RECORDS MANAGEMENT. SEC. 105.1 AND SEC. 107.2.1.4 CITY |
| | AMENDMENTS. NOTE: THERE IS NO ADDITIONAL FEES FOR THE |
| | SEPARATE PERMIT APPLICATIONS. PLEASE COORDINATE WITH |
| | MIKE ORIO ( SEE CONTACT INFORMATION BELOW) FOR PROPER |
| | ADDRESSING OF EACH TENANT. |
| | |
| | MICHAEL P ORIO |
| | GIS SUPPORT SPECIALIST |
| | INFORMATION TECHNOLOGY |
| | |
| | PHONE: 494-1040 EXT: 1080 |
| | FAX: 494-1117 |
| | E-MAIL: [email protected] |
| | |
| | -NOTE: |
| | PLANS SUBMITTED DON'T SHOW THE ENCLOSED ELEVATOR LOBBY. |
| | THIS BUILDING WAS ORIGINALLY DESIGNED WITH ENCLOSED |
| | ELEVATOR LOBBY. COORDINATE WITH PERMIT #17080045 FOR |
| | THE RECONSTRUCTION OF ELEVATOR LOBBY. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| | |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY |
| | REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS. |
| | |
| | |