| 2018-04-30 16:40:38 | 04/30/18 DENIED BY PLUMBING |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | 1. PLUMBING RISER DIAGRAM NEEDS VENTS FOR LAUNDRY TRAY, |
| | GUESS BATH AND MASTER NEED TO BE VENTED CORRECTLY, 2017 |
| | FBC R3004, R3005, |
| | 2. PLEASE PROVIDE WATER SUPPLY AND DISTRIBUTION SYSTEM |
| | DESIGN FOR WATER RISER DIAGRAM, WPB AMENDMENTS TO THE |
| | FBC SEC. 107.3.5.3 (11) RESIDENTIAL PLUMBING |
| | 3. SIGNATURE (OR SEAL, OR TITLE BLOCK, OR ALL THREE) |
| | ARE NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE |
| | 61G15-23.001, FLORIDA STATUTE 471. |
| | 4. PLANS ARE REQUIRED TO BE DESIGNED AND SIGNED AND |
| | SEALED BY A LICENSED ENGINEER OR ARCHITECT. PROVIDE |
| | CORRECTION. FS 471.003(2)(H); 471.025; FBC 107.2.1, |
| | 107.3.5 |
| | 5. ROMAN TUB STANDALONE REQUIRED A CONTROL VALVE BY A |
| | WATER TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3, EXCEPT WHERE SUCH PROTECTION IS |
| | OTHERWISE PROVIDED BY A COMBINATION TUB/SHOWER VALVE IN |
| | ACCORDANCE WITH SECTION P2708.4. FBC R 2713.3 BATHTUB |
| | AND WHIRLPOOL BATHTUB VALVES. |
| | 6. ON THE ROOM LABELLED POWER AND MASTER THE SHOWER PAN |
| | IS NOT RECEDED IT WILL REQUIRE LINING, 2017 FBC R |
| | 2709.2 |
| | 7. SHOWER MEASUREMENT IN POWER IS AT 30? PLUS 4? FOR |
| | CURB WHICH IS NOT SHOWN AND WATER CLOSET SHALL NOT BE |
| | SET CLOSER THAN 15? INCHES FROM ITS CENTER TO ANY SIDE |
| | WALL, PARTITION, VANITY OR OTHER OBSTRUCTION, OR CLOSER |
| | THAN 30? INCHES CENTER TO CENTER BETWEEN ADJACENT |
| | FIXTURES. THE SHOWER MAY BE SMALLER AS LONG AS IT |
| | COMPLIES WITH A SHOWER COMPARTMENT THAT IS NOT LESS |
| | THAN 900 SQUARE INCHES, PLEASE PROVIDE SHOWER DRAIN |
| | DETAILS AND COMPLIANCE. WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | [email protected] |
| | 561-805-6720 |
| | |