| Plan Review Notes For Permit 18040474 |
| Permit Number |
18040474 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-04-16 13:12:33 | PERMIT # 18040474 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | 1) UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF | | | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE | | | 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA | | | AMENDMENTS. | | | | | | 2) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION | | | SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND | | | RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION | | | SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A | | | 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A | | | FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED | | | BY EMAIL ([email protected]) OR IN WRITING (FAX: | | | 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE | | | MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.? | | | | | | 3) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | | SYSTEM AND/OR FIRE ALARM SYSTEM. | | | | | | 4) PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY | | | TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, | | | EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF | | | TRAVEL, ETC. | | | | | | 5) PROVIDE A SITE LAYOUT INDICATING THE | | | FURNITURE/SEATING TO BE USED AND PLACEMENT. MAY BE | | | INCLUDED IN THE LIFE SAFETY SHEET. | | | | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | [email protected] | | | |
|