| Date |
Text |
| 2018-04-27 17:14:42 | 04/27/18 DENIED BY PLUMBING |
| | |
| | 1. SIGNATURE (OR SEAL, OR TITLE BLOCK, OR ALL THREE) |
| | ARE NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE |
| | 61G15-23.001, FLORIDA STATUTE 471. WPB AMENDMENTS TO |
| | THE FBC SEC. 107.1 GENERAL. |
| | |
| | 2. PLANS ARE REQUIRED TO BE DESIGNED AND SIGNED AND |
| | SEALED BY A LICENSED ENGINEER OR ARCHITECT. PLANS |
| | FURNISHED BY AN INTERIOR DESIGNER ARE NOT ACCEPTABLE. |
| | PROVIDE CORRECTION. FS 471.003(2)(H); 471.025; FBC |
| | 107.2.1, 107.3.5 |
| | |
| | 3.THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON THE |
| | APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED |
| | CONTRACT. WPB AMENDMENTS TO THE FBC 109.3. BUILDING |
| | PERMITS VALUATIONS. IF IN THE OPINION OF THE BUILDING |
| | OFFICIAL, THE CLAIMED VALUATION OF BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR |
| | PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE |
| | APPLICATION, THE PERMIT SHALL BE DENIED UNLESS THE |
| | APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR |
| | BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO |
| | MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR |
| | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS |
| | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |