| 2019-08-07 17:55:57 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | 5TH BUILDING REVIEW DENIED: | | | | | | 1. PROVIDE PRODUCT APPROVALS REVIEWED AND APPROVED BY | | | DESIGNER OF RECORD. | | | | | | 2. PROVIDE UPDATED ENERGY CALCULATIONS THAT CORRELATE | | | WITH PLANS. | | | (THE DOORS AND WINDOWS FROM THE PLANS NEED TO BE | | | INCLUDED IN THE ENERGY CALCULATIONS). | | | | | | 3. THE ELEVATION CERTIFICATE NEEDS TO BE CORRECTED, | | | (SEE SUBMITTAL # 19080006). | | | | | | PROVISO: THE INSULATION AT BLOCK WALLS NEEDS TO | | | CORRELATE WITH INSULATION ON ENERGY CALCULATIONS AS | | | FOLLOWS (R=4.2). | | | | | | |
|