Plan Review Notes
Plan Review Notes For Permit 18040403
Permit Number 18040403
Review Stop B
Sequence Number 2
Notes
Date Text
2018-05-03 12:17:2405/03/18 RESPONSE TO STEPHEN ROY'S (ARCH.) E-MAIL:
  
 GOOD MORNING MR. ROY,
 AS PER OUR PHONE CONVERSATION, I TOLD YOU THAT I WAS
 USING THE COST PER SQUARE FOOT VALUE THAT WAS SUBMITTED
 BY THE LICENSED PROPERTY APPRAISER FOR PUBLIC RECORDS.
 THIS APPRAISAL WAS THE BASE THAT WAS USED TO DETERMINE
 THAT THE PROPOSED ADDITION WOULD NOT EXCEED THE 50%
 VALUE OF THE STRUCTURE. THE PROPOSED REVISION/ADDITION
 TO THE APPROVED PERMIT SET BRINGS UP THE VALUE OVER THE
 50% WHEN THE OVERALL VALUE OF THE PROPOSED IMPROVEMENT
 IS TAKEN INTO CONSIDERATION. THE FACT IS THAT I AM
 USING THE $300 PER SQUARE FOOT COST FOR THE OVERALL
 CONSTRUCTION. I TOLD YOU I HAVE MADE MY CALL BASED ON
 THE VALUE SPECIFIED BY THE LICENSED APPRAISER. THAT'S
 WHY I ADVICE YOU TO CONTACT THE BUILDING OFFICIAL FOR
 HIS FINAL DECISION.
 REGARDS
 JULIO C. GOMEZ
 CITY OF WEST PALM BEACH
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
  
 FROM: "MR. STEPHEN ROY"
 TO: [email protected]
 CC: [email protected]
 DATE: 05/02/2018 11:14 AM
 SUBJECT: [CAUTION: MESSAGE CONTAINS REDIRECT URL
 CONTENT] RE: REVISION 18040403 / MCCAFFREY 4821 S
 FLAGLER DR. ? PENDING BUILDING COMMENTS
  
 SORRY, I WAS HOPING TO MEET TOMORROW. ARE YOU AVAILABLE
 AT NOON OR BEFORE 3:30? IF YOU REVIEW THE ESTIMATE AND
 ACCEPT THEN THERE IS NO NEED TO MEET.
 I HAVE ATTACHED THE UPDATED PRICING FROM HEDRICK
 BROTHERS WHICH INCLUDED THE S.F. INCREASE.
  
 REGARDS,
 STEPHEN ROY, ARCHITECT
 ROY & POSEY
 ARCHITECTURE | LANDSCAPE | INTERIORS
  
 2417 SOUTH DIXIE HWY (MAP)
 WEST PALM BEACH, FLORIDA 33401
 OFFICE: 561-659-5683
 [email protected]
  
  
 ON MAY 2, 2018, AT 8:22 AM, [email protected] WROTE:
  
 GOOD MORNING MR. ROY,
 PLEASE CHECK THE DATE 5/5/18 IS FOR SATURDAY. MY
 SCHEDULE IS MORE FLEXIBLE THAN ROBERT BROWN. I THINK IS
 BETTER TO CONTACT HIM DIRECTLY. I WILL TRY ACCOMMODATE
 MY SCHEDULE TO THE PROPOSED DATE AND TIME.
 REGARDS,
  ROBERT A BROWN
 BUILDING OFFICIAL
 DEVELOPMENT SERVICES
 BUILDING INSPECTIONS
  
 
 401 CLEMATIS STREET
 P.O.BOX 3366
 WEST PALM BEACH, FL 33402
 PHONE: 805-6700 EXT: 6652
 FAX: 805-6731
 E-MAIL: [email protected]
 SERVING SINCE OCT 21, 2001
 EMPLOYMENT CATEGORY: FR
 SUPERVISOR: GREENE, RICHARD EDWARD
  
 JULIO C. GOMEZ
 CITY OF WEST PALM BEACH
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
  
 HOW ARE WE DOING? PLEASE LET US KNOW BY TAKING AN
 ANONYMOUS SURVEY AT:
 HTTP://WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSE
 RVICES
  
 FROM: "MR. STEPHEN ROY"
 TO: [email protected]
 CC: ERIN BRODSKY
 DATE: 05/01/2018 01:47 PM
 SUBJECT: [CAUTION: MESSAGE CONTAINS REDIRECT URL
 CONTENT] 18040403 / MCCAFFREY 4821 S FLAGLER DR. ?
 PENDING BUILDING COMMENTS
  
 HELLO MR GOMEZ,
 I SPOKE TO ERIN FROM HEDRICK BROTHER TODAY REGARDING
 THE VALUE OF CONSTRUCTION FOR THE MCCAFFERY RESIDENCE.
 WE WOULD LIKE TO SCHEDULE A MEETING WITH YOU AND MR.
 BROWN THIS THURSDAY 5/5/18 ANYTIME BETWEEN NOON AND
 3:30. PLEASE ADVISE WHAT WORKS BEST FOR YOU.
 REGARDS,
 STEPHEN ROY, ARCHITECT
  
 ROY & POSEY
 ARCHITECTURE | LANDSCAPE | INTERIORS
  
 2417 SOUTH DIXIE HWY (MAP)
 WEST PALM BEACH, FLORIDA 33401
 OFFICE: 561-659-5683
 [email protected]
  
 FWD:
 RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS
 CODE: FBC 5TH EDITION (2014).
  
 1-THIS HOUSE IS LOCATED IN FLOOD ZONE AE (BFE 6). IT
 LOOKS LIKE THE OVERALL ADDITION, INCLUDING THIS
 REVISION EXCEEDS THE 50 PERCENT VALUE OF THE EXISTING
 STRUCTURE. BY USING THE SAME REPLACEMENT COSTS PER
 SQUARE FOOT ($300.00) USED BY JOHN B. TRUAX ON THE
 PROPERTY APPRAISAL DATED 02/02/2018 SUBMITTED TO OBTAIN
 THE BUILDING PERMIT 17110530, THE PROPOSED
 ADDITION/REVISION EXCEEDS THE 50 PERCENT VALUE OF THE
 EXISTING STRUCTURE. THEREFORE, THIS REVISION IS
 CONSIDERED A SUBSTANTIAL IMPROVEMENT. SUBSTANTIAL
 IMPROVEMENT REQUIRES THE EXISTING HOUSE AND THE
 PROPOSED ADDITION TO BE 2 FEET ABOVE THE BASE FLOOD
 ELEVATION AS REQUIRED BY CITY ORDINANCE SEC. 18-33.
 PROVIDE COMPLIANCE WITH THE REQUIRED FINISH FLOOR
 ELEVATION. SPECIFY THE PROPOSED FINISH FLOOR ELEVATIONS
 ON ALL PLANS, SURVEYS, ETC.
  
 SEC. 18-33. - TECHNICAL AMENDMENTS TO FLORIDA BUILDING
 CODE, RESIDENTIAL.
 1. CODE OF ORDINANCES
 2. CHAPTER 18 - BUILDINGS AND BUILDING REGULATIONS
 3. ARTICLE II. - BUILDING CODE STRUCTURES IN FLOOD
 HAZARD AREAS NOT DESIGNATED AS COASTAL A ZONES SHALL
 HAVE THE LOWEST FLOORS ELEVATED TO OR ABOVE THE BASE
 FLOOD ELEVATION PLUS TWO FEET OR THE DESIGN FLOOD
 ELEVATION.
 SUBSTANTIAL IMPROVEMENT: SUBSTANTIAL IMPROVEMENT MEANS
 ANY COMBINATION OF REPAIR, RECONSTRUCTION,
 REHABILITATION, ALTERATION, ADDITION, OR OTHER
 IMPROVEMENT OF A BUILDING OR STRUCTURE, FOR WHICH THE
 CUMULATIVE COST IN ANY FIVE YEAR PERIOD EQUALS OR
 EXCEEDS 50 PERCENT OF THE MARKET VALUE OF THE BUILDING
 OR STRUCTURE AT THE END OF THE FIVE YEAR PERIOD AND
 BEFORE THE IMPROVEMENT OR REPAIR IS STARTED. IF THE
 STRUCTURE HAS INCURRED "SUBSTANTIAL DAMAGE," ANY
 REPAIRS ARE CONSIDERED SUBSTANTIAL IMPROVEMENT
 REGARDLESS OF THE ACTUAL REPAIR WORK
 PERFORMED.
  
  
 2- REVISED MASTER BEDROOM DOESN'T PROVIDE THE EMERGENCY
 ESCAPE AND RESCUE OPENING REQUIRED BY SEC. R310.
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 3- CLARIFY ATTIC ACCESS LOCATION AND SPECIFY SIZE.
 ATTIC ACCESS IS LOCATED IN THE OFFICE. ACCORDING TO
 ROOF FRAMING PLAN, THIS ROOM HAS A VAULTED CEILING.
 REVISE AS REQUIRED AND PROVIDE ATTIC ACCESS SIZE. SEC.
 R807 FBC-RESIDENTIAL.
  
 4- MISSING NEW FLITCH BEAM DETAIL 5 SPECIFIED ON THE
 ROOF FRAMING PLAN BY THE STAIRWAY BEARING WALL. PROVIDE
 DETAIL AND SPECIFICATIONS. SEC. R301.1 FBC-RESIDENTIAL.
  
 5-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR THE BEAD BOARD SOFFIT SPECIFIED ON
 PLANS/SECTIONS.
  
 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 NOTE:
  
 ELEVATION CERTIFICATES REQUIRED DURING CONSTRUCTION.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
 ****PROVISO REMAINDER*******
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE MANUFACTURER'S DETAILS & SPECS FOR FACTORY
 BUILT FIREPLACE & CLAY FLUE SPECIFIED ON FLOOR PLANS
 AND SHEET A.13. SHOW COMPLIANCE WITH UL 127.
 2- SOIL TEST REPORT TO HAVE ORIGINAL SEAL AND
 SIGNATURE. THIS IS NOT A DIGITAL SUBMITTAL.
  
 IMPORTANT: ELEVATION CERTIFICATES WILL BE REQUIRED
 DURING CONSTRUCTION.
  
  
  
 *******************************************************
 *******************************************************
 *******************************************************
 *******
  
 RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS
 CODE: FBC 5TH EDITION (2014).
  
 1-THIS HOUSE IS LOCATED IN FLOOD ZONE AE (BFE 6). IT
 LOOKS LIKE THE OVERALL ADDITION, INCLUDING THIS
 REVISION EXCEEDS THE 50 PERCENT VALUE OF THE EXISTING
 STRUCTURE. BY USING THE SAME REPLACEMENT COSTS PER
 SQUARE FOOT ($300.00) USED BY JOHN B. TRUAX ON THE
 PROPERTY APPRAISAL DATED 02/02/2018 SUBMITTED TO OBTAIN
 THE BUILDING PERMIT 17110530, THE PROPOSED
 ADDITION/REVISION EXCEEDS THE 50 PERCENT VALUE OF THE
 EXISTING STRUCTURE. THEREFORE, THIS REVISION IS
 CONSIDERED A SUBSTANTIAL IMPROVEMENT. SUBSTANTIAL
 IMPROVEMENT REQUIRES THE EXISTING HOUSE AND THE
 PROPOSED ADDITION TO BE 2 FEET ABOVE THE BASE FLOOD
 ELEVATION AS REQUIRED BY CITY ORDINANCE SEC. 18-33.
 PROVIDE COMPLIANCE WITH THE REQUIRED FINISH FLOOR
 ELEVATION. SPECIFY THE PROPOSED FINISH FLOOR ELEVATIONS
 ON ALL PLANS, SURVEYS, ETC.
  
 SEC. 18-33. - TECHNICAL AMENDMENTS TO FLORIDA BUILDING
 CODE, RESIDENTIAL.
 1. CODE OF ORDINANCES
 2. CHAPTER 18 - BUILDINGS AND BUILDING REGULATIONS
 3. ARTICLE II. - BUILDING CODE
 STRUCTURES IN FLOOD HAZARD AREAS NOT DESIGNATED AS
 COASTAL A ZONES SHALL HAVE THE LOWEST FLOORS ELEVATED
 TO OR ABOVE THE BASE FLOOD ELEVATION PLUS TWO FEET OR
 THE DESIGN FLOOD ELEVATION
  
 SUBSTANTIAL IMPROVEMENT:
 SUBSTANTIAL IMPROVEMENT MEANS ANY COMBINATION OF
 REPAIR, RECONSTRUCTION, REHABILITATION, ALTERATION,
 ADDITION, OR OTHER IMPROVEMENT OF A BUILDING OR
 STRUCTURE, FOR WHICH THE CUMULATIVE COST IN ANY FIVE
 YEAR PERIOD EQUALS OR EXCEEDS 50 PERCENT OF THE MARKET
 VALUE OF THE BUILDING OR STRUCTURE AT THE END OF THE
 FIVE YEAR PERIOD AND BEFORE THE IMPROVEMENT OR REPAIR
 IS STARTED. IF THE STRUCTURE HAS INCURRED "SUBSTANTIAL
 DAMAGE," ANY REPAIRS ARE CONSIDERED SUBSTANTIAL
 IMPROVEMENT REGARDLESS OF THE ACTUAL REPAIR WORK
 PERFORMED.
  
 2- REVISED MASTER BEDROOM DOESN'T PROVIDE THE EMERGENCY
 ESCAPE AND RESCUE OPENING REQUIRED BY SEC. R310.
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 3- CLARIFY ATTIC ACCESS LOCATION AND SPECIFY SIZE.
 ATTIC ACCESS IS LOCATED IN THE OFFICE. ACCORDING TO
 ROOF FRAMING PLAN, THIS ROOM HAS A VAULTED CEILING.
 REVISE AS REQUIRED AND PROVIDE ATTIC ACCESS SIZE. SEC.
 R807 FBC-RESIDENTIAL.
  
 4- MISSING NEW FLITCH BEAM DETAIL 5 SPECIFIED ON THE
 ROOF FRAMING PLAN BY THE STAIRWAY BEARING WALL. PROVIDE
 DETAIL AND SPECIFICATIONS. SEC. R301.1 FBC-RESIDENTIAL.
  
 5-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR THE BEAD BOARD SOFFIT SPECIFIED ON
 PLANS/SECTIONS.
  
 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 NOTE:
 ELEVATION CERTIFICATES REQUIRED DURING CONSTRUCTION.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
 ****PROVISO REMAINDER*******
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE MANUFACTURER'S DETAILS & SPECS FOR FACTORY
 BUILT FIREPLACE & CLAY FLUE SPECIFIED ON FLOOR PLANS
 AND SHEET A.13. SHOW COMPLIANCE WITH UL 127.
 2- SOIL TEST REPORT TO HAVE ORIGINAL SEAL AND
 SIGNATURE. THIS IS NOT A DIGITAL SUBMITTAL.
  
 IMPORTANT: ELEVATION CERTIFICATES WILL BE REQUIRED
 DURING CONSTRUCTION.
  