Plan Review Notes
Plan Review Notes For Permit 18040403
Permit Number 18040403
Review Stop B
Sequence Number 1
Notes
Date Text
2018-04-24 17:39:42RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS
 CODE: FBC 5TH EDITION (2014).
  
 1-THIS HOUSE IS LOCATED IN FLOOD ZONE AE (BFE 6). IT
 LOOKS LIKE THE OVERALL ADDITION, INCLUDING THIS
 REVISION EXCEEDS THE 50 PERCENT VALUE OF THE EXISTING
 STRUCTURE. BY USING THE SAME REPLACEMENT COSTS PER
 SQUARE FOOT ($300.00) USED BY JOHN B. TRUAX ON THE
 PROPERTY APPRAISAL DATED 02/02/2018 SUBMITTED TO OBTAIN
 THE BUILDING PERMIT 17110530, THE PROPOSED
 ADDITION/REVISION EXCEEDS THE 50 PERCENT VALUE OF THE
 EXISTING STRUCTURE. THEREFORE, THIS REVISION IS
 CONSIDERED A SUBSTANTIAL IMPROVEMENT. SUBSTANTIAL
 IMPROVEMENT REQUIRES THE EXISTING HOUSE AND THE
 PROPOSED ADDITION TO BE 2 FEET ABOVE THE BASE FLOOD
 ELEVATION AS REQUIRED BY CITY ORDINANCE SEC. 18-33.
 PROVIDE COMPLIANCE WITH THE REQUIRED FINISH FLOOR
 ELEVATION. SPECIFY THE PROPOSED FINISH FLOOR ELEVATIONS
 ON ALL PLANS, SURVEYS, ETC.
  
 SEC. 18-33. - TECHNICAL AMENDMENTS TO FLORIDA BUILDING
 CODE, RESIDENTIAL.
 1. CODE OF ORDINANCES
 2. CHAPTER 18 - BUILDINGS AND BUILDING REGULATIONS
 3. ARTICLE II. - BUILDING CODE
 STRUCTURES IN FLOOD HAZARD AREAS NOT DESIGNATED AS
 COASTAL A ZONES SHALL HAVE THE LOWEST FLOORS ELEVATED
 TO OR ABOVE THE BASE FLOOD ELEVATION PLUS TWO FEET OR
 THE DESIGN FLOOD ELEVATION
  
 SUBSTANTIAL IMPROVEMENT:
 SUBSTANTIAL IMPROVEMENT MEANS ANY COMBINATION OF
 REPAIR, RECONSTRUCTION, REHABILITATION, ALTERATION,
 ADDITION, OR OTHER IMPROVEMENT OF A BUILDING OR
 STRUCTURE, FOR WHICH THE CUMULATIVE COST IN ANY FIVE
 YEAR PERIOD EQUALS OR EXCEEDS 50 PERCENT OF THE MARKET
 VALUE OF THE BUILDING OR STRUCTURE AT THE END OF THE
 FIVE YEAR PERIOD AND BEFORE THE IMPROVEMENT OR REPAIR
 IS STARTED. IF THE STRUCTURE HAS INCURRED "SUBSTANTIAL
 DAMAGE," ANY REPAIRS ARE CONSIDERED SUBSTANTIAL
 IMPROVEMENT REGARDLESS OF THE ACTUAL REPAIR WORK
 PERFORMED.
  
 2- REVISED MASTER BEDROOM DOESN'T PROVIDE THE EMERGENCY
 ESCAPE AND RESCUE OPENING REQUIRED BY SEC. R310.
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 3- CLARIFY ATTIC ACCESS LOCATION AND SPECIFY SIZE.
 ATTIC ACCESS IS LOCATED IN THE OFFICE. ACCORDING TO
 ROOF FRAMING PLAN, THIS ROOM HAS A VAULTED CEILING.
 REVISE AS REQUIRED AND PROVIDE ATTIC ACCESS SIZE. SEC.
 R807 FBC-RESIDENTIAL.
  
 4- MISSING NEW FLITCH BEAM DETAIL 5 SPECIFIED ON THE
 ROOF FRAMING PLAN BY THE STAIRWAY BEARING WALL. PROVIDE
 DETAIL AND SPECIFICATIONS. SEC. R301.1 FBC-RESIDENTIAL.
  
 5-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR THE BEAD BOARD SOFFIT SPECIFIED ON
 PLANS/SECTIONS.
  
 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 NOTE:
 ELEVATION CERTIFICATES REQUIRED DURING CONSTRUCTION.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
 ****PROVISO REMAINDER*******
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE MANUFACTURER'S DETAILS & SPECS FOR FACTORY
 BUILT FIREPLACE & CLAY FLUE SPECIFIED ON FLOOR PLANS
 AND SHEET A.13. SHOW COMPLIANCE WITH UL 127.
 2- SOIL TEST REPORT TO HAVE ORIGINAL SEAL AND
 SIGNATURE. THIS IS NOT A DIGITAL SUBMITTAL.
  
 IMPORTANT: ELEVATION CERTIFICATES WILL BE REQUIRED
 DURING CONSTRUCTION.
  