| Plan Review Notes For Permit 18040394 |
| Permit Number |
18040394 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-04-12 13:54:27 | 04/12/2018 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE | | | A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME | | | AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED | | | UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | THE CODE REQUIRES THAT LAUNDRY FACILITIES NOT INSTALLED | | | WITHIN AN INDIVIDUAL DWELLING UNIT OR INTENDED FOR | | | INDIVIDUAL FAMILY USE SHALL BE EQUIPPED WITH AN | | | INTERCEPTOR WITH A WIRE BASKET OR SIMILAR DEVICE, | | | REMOVABLE FOR CLEANING, THAT PREVENTS PASSAGE INTO THE | | | DRAINAGE SYSTEM OF SOLIDS 1/2 INCH (12.7 MM) OR LARGER | | | IN SIZE, STRING, RAGS, BUTTONS OR OTHER MATERIALS | | | DETRIMENTAL TO THE PUBLIC SEWAGE SYSTEM. FBC P 1003.6 | | | LAUNDRIES. THE SPECIFICATION YOU PROVIDED IS A FILTER | | | SYSTEM AND NOT CLASSIFIED AS AN INTERCEPTOR ASSEMBLY. | | | PLEASE PROVIDE A DIFFERENT INTERCEPTOR SPECIFICATION. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | [email protected] | | | 561-805-6720 | | | | | | |
|