Plan Review Notes
Plan Review Notes For Permit 18040394
Permit Number 18040394
Review Stop P
Sequence Number 1
Notes
Date Text
2018-04-12 13:54:2704/12/2018 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE
 A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 THE CODE REQUIRES THAT LAUNDRY FACILITIES NOT INSTALLED
 WITHIN AN INDIVIDUAL DWELLING UNIT OR INTENDED FOR
 INDIVIDUAL FAMILY USE SHALL BE EQUIPPED WITH AN
 INTERCEPTOR WITH A WIRE BASKET OR SIMILAR DEVICE,
 REMOVABLE FOR CLEANING, THAT PREVENTS PASSAGE INTO THE
 DRAINAGE SYSTEM OF SOLIDS 1/2 INCH (12.7 MM) OR LARGER
 IN SIZE, STRING, RAGS, BUTTONS OR OTHER MATERIALS
 DETRIMENTAL TO THE PUBLIC SEWAGE SYSTEM. FBC P 1003.6
 LAUNDRIES. THE SPECIFICATION YOU PROVIDED IS A FILTER
 SYSTEM AND NOT CLASSIFIED AS AN INTERCEPTOR ASSEMBLY.
 PLEASE PROVIDE A DIFFERENT INTERCEPTOR SPECIFICATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  
  