| 2018-04-18 12:12:48 | BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017). |
| | |
| | 1- SCOPE OF WORK IS NOT CLEAR. THE PROJECT SCOPE OF THE |
| | COVER SHEET STATES "DEMOLITION OF EXISTING 1,627 +/- |
| | SQFT TENANT SPACE". SHEET A-1.00 SHOWS DEMOLITION AND |
| | NEW WORK: STOREFRONT AND INFILL ON REAR WALL. CLARIFY |
| | IF THE INTENTION OF THIS PERMIT APPLICATION IS FOR |
| | DEMOLITION ONLY PERMIT OR TO CONVERT THE SPACE INTO A |
| | SHELL SPACE ONLY. CLEARLY STATE IT IN PLANS. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | 2- ADDRESS OF PROPOSED WORK IS NOT CLEAR. PERMIT |
| | APPLICATION STATES 831 VILLAGE BLVD #901. ARCHITECTURAL |
| | PLANS STATES 931 VILLAGE BLVD # SUITE 901 AND CITY |
| | RECORDS (BASED ON THE PARCEL ID #) IDENTIFIES THIS |
| | BUILDING AS 831 VILLAGE BLVD #901. PLEASE COORDINATE |
| | CORRECT ADDRESS TO AVOID CONFLICT/DELAYS. SEC. 107.2.1 |
| | CITY AMENDMENTS. |
| | |
| | NOTE: COORDINATE CORRECT ADDRESS WITH MICHAEL P ORIO |
| | GIS SUPPORT SPECIALIST |
| | INFORMATION TECHNOLOGY |
| | GIS |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33401 |
| | PHONE: 494-1040 EXT: 1080 |
| | FAX: 494-1117 |
| | E-MAIL: [email protected] |
| | |
| | 3- A) PROVIDE ADDITIONAL FLOOR PLAN SHOWING THE |
| | PROPOSED STOREFRONT. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | B) PROVIDE DETAILS AND SPECIFICATIONS SHOWING |
| | COMPLIANCE WITH THE FBC ACCESSIBILITY FOR THE NEW |
| | STOREFRONT DOORS. SEC. 206.4 FBC-ACCESSIBILITY. |
| | |
| | C) MISSING THE SILL, JAMB AND HEAD DETAILS (SHEET |
| | A-602) SPECIFIED ON THE DOOR AND WINDOW SCHEDULES. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | 4- WINDOWS AND DOORS DESIGN PRESSURES SPECIFIED ON |
| | SHEET A-4.00. SPECIFY THE BUILDING MEAN ROOF HEIGHT, |
| | BUILDING EXPOSURE, OPENING LOCATION (INTERIOR OR END). |
| | NOTE: THE DESIGN PRESSURES NEED TO BE BASED ON THE |
| | TRIBUTARY AREA OF THE WINDOW/DOORS. REVISE DESIGN |
| | PRESSURES ACCORDINGLY. SEC. 1609.6.4.4.1 FBC. |
| | |
| | 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | A) ENTRY DOORS WITH TRANSOM ABOVE AS SHOWN ON PLANS. |
| | |
| | B) STOREFRONT WINDOWS AS SHOWN PLANS. NOTE: IDENTIFY |
| | GLAZING/ MULLIONS. FOR ALL PRODUCTS WITH GLAZING, |
| | PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF |
| | GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS |
| | AND ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 |
| | FBC-B 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL |
| | BE INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS |
| | |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| | |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY |
| | REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |