| Plan Review Notes For Permit 18040360 |
| Permit Number |
18040360 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-04-24 13:20:41 | | | | 1ST REVIEW: FBC 2017 6TH EDITION | | | PLUMBING COMMENTS: | | | | | | 1. WASHING MACHING IS MISSING FROM SANITARY ISOMETRIC | | | IT SHALL CONNECT DOWN STREAM OF BATHROOM GROUP. PER FBC | | | PL 912.1 | | | | | | 2. SHOW THE VENTS ON TOP OF THESTACK FOR THE SINKS. | | | EACH FIXTURE SHALL BE VENTED. PER FBC PL 901.2. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|