| 2018-09-25 16:28:55 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED BY PERSON |
| | RESPONSIBLE FOR DESIGN. FS 471.003(2)(H); 471.025; WPB |
| | FBC 107.2.1, 107.3.5 9 (ELECTRICAL PLAN IS REQUIRED TO |
| | BE SIGNED BY PERSON RESPONSIBLE FOR THE DESIGN. PROVIDE |
| | CORRECTION. FS 481.229; WPB FBC 107.2.1, 107.3.5.1.2) |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | |
| | NEW COMMENT: |
| | |
| | 4. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. IT |
| | APPEARS THE ELECTRICAL IS NOT INCLUDED IN THE CONTRACT |
| | PROVIDED. FBC 109.3 |
| | 5. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP |
| | CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. |
| | PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE |
| | E3703.4, E3901.6 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |