| 2018-04-30 12:53:43 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. IT APPEARS THAT THE WRONG CODE WAS USED FOR DESIGN |
| | AS THERE ARE SEVERAL CODE SECTIONS QUOTED FROM THE FBC, |
| | RESIDENTIAL. THE PROVISIONS OF THE FLORIDA BUILDING |
| | CODE, RESIDENTIAL SHALL APPLY TO THE CONSTRUCTION, |
| | ALTERATION, MOVEMENT, ENLARGEMENT, REPLACEMENT, REPAIR, |
| | EQUIPMENT, USE AND OCCUPANCY, LOCATION, REMOVAL AND |
| | DEMOLITION OF DETACHED ONE- AND TWO-FAMILY DWELLINGS |
| | AND TOWNHOUSES NOT MORE THAN THREE STORIES ABOVE GRADE |
| | PLANE IN HEIGHT WITH A SEPARATE MEANS OF EGRESS AND |
| | THEIR ACCESSORY STRUCTURES NOT MORE THAN THREE STORIES |
| | ABOVE GRADE PLANE IN HEIGHT. REMOVE ANY NOTES THAT |
| | QUOTE THE FBC RESIDENTIAL CODE.PROVIDE CORRECTION. FBC |
| | RE R101.2; FBC 107.2.1 |
| | 2. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D) |
| | 3. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12 |
| | 4. SHOW LOCATION OF PANEL TO BE RELOCATED TO CONFIRM |
| | CODE COMPLIANCE. FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |