| Notes |
| Date |
Text |
| 2018-04-12 19:18:24 | 04/12/2018 1ST PLUMBING REVIEW**DENIED** | | | | | | 1) STUDIO BATHROOM IS SHOWING A OVERALL MEASURMENT OF | | | 4' 6". THE MIN REQUIRED WOULD BE 5' (60") FINISHED TO | | | COMPLY WITH FBC-R P2705. EACH FIXTURE REQUIRES 30" | | | OVERALL. YOUR ROOM IS 6" TO SMALL. | | | | | | 2) SHOW 2ND TANKLESS LOCATION. FBC 107.2.1 | | | | | | 3) EXPLAIN HOW YOU INTEND TO HAVE ACCESS TO THE SHUT | | | OFF VALVES OR THE WASHING MACHINE TO COMPLY WITH FBC-R | | | P2903.9.3 | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|