2018-04-17 10:14:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOTE ON PLAN STATES THAT ALL RECEPTACLES EXCEPT GFI
 WILL BE ARC FAULT PROTECTED. THIS STATEMENT IS NOT CODE
 COMPLIANT. PER CODE: ?ALL BRANCH CIRCUITS THAT SUPPLY
 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS
 INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS,
 LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI
 PROTECTED.? PROVIDE CORRECTION. NEC 210.12; FBC RE
 E3902.16
 2. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. BOTH BATHROOMS
 ARE SHOWN WITH #14 WIRE ON A 15 AMP BREAKER. PROVIDE
 CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4
 3. ONE OF THE BATHROOMS DOES NOT SHOW THE REQUIRED
 RECEPTACLE. A GFCI PROTECTED OUTLET ON A 20 AMP CIRCUIT
 IS REQUIRED WITHIN 3 FEET OF EACH BASIN. PROVIDE
 CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE
 E3703.4, E3901.6
 4. LAYOUT ON RISER DIAGRAM DOES NOT MATCH WHAT IS SHOWN
 ON PLAN. SHOW SERVICE LOCATION AND PANEL LOCATION TO
 CONFIRM CODE COMPLIANCE. FBC 107.2.1
 5. LIGHTING IN CLOSET IS NOT SPECIFIED. PER CODE:
 "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND
 PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE
 PERMITTED IN CLOTHES CLOSETS". PROVIDE CORRECTION OR
 NOTE THAT INSTALLATION WILL COMPLY. NEC 410.16; FBC RE
 E4003.12
 6. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 7. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 8. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9
 9. RISER DIAGRAM SHOWS AN EXISTING 100 AMP FEED.
 PROVIDE ACCURATE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 10. OCP LISTED ON PANEL SCHEDULE FOR MECHANICAL
 EQUIPMENT DOES NOT MATCH WHAT IS SPECIFIED ON
 MECHANICAL DRAWING. THE AMPACITY OF THE CONDUCTORS
 SUPPLYING MULTIMOTOR AND COMBINATION LOAD EQUIPMENT
 SHALL NOT BE LESS THAN THE MINIMUM CIRCUIT AMPACITY
 MARKED ON THE EQUIPMENT. THE BRANCH CIRCUIT OVERCURRENT
 PROTECTION DEVICE RATING SHALL BE THE SIZE AND TYPE
 MARKED ON THE EQUIPMENT. NEC 440.4(B), 440.35,
 440.62(A); FBC RE E3702.11
 11. PANEL SCHEDULE STATES THE MAIN BUS SIZE AS 225 AMP,
 BUT DOES NOT STATE THE MAIN BREAKER SIZE. PROVIDE
 CLARIFICATION. FBC 107.2.1; NEC 215.5
 12. NOTE ABOVE PANEL SCHEDULE STATES THAT THE
 ELECTRICAL GEAR SHALL BE LABELED WITH ARC FAULT
 LABELING AND METER SHOULD BE MOUNTED AT 12? ABOVE
 GRADE. ARC FAULT LABELING IS NOT REQUIRED FOR
 RESIDENTIAL INSTALLATIONS. FPL SERVICE STANDARDS
 REQUIRE THE METER CENTER TO BE MOUNTED BETWEEN 5? TO
 6?. NEC 110.24; FBC 107.2.1
 13. ONLY ONE SMALL APPLIANCE CIRCUIT IS SHOWN ON PANEL
 SCHEDULE AND PLAN FOR COUNTER TOP RECEPTACLES IN THE
 KITCHEN. A MINIMUM OF 2 CIRCUITS IS REQUIRED IN LOAD
 CALCULATION AND TO BE USED IN WIRING OF COUNTER TOP
 RECEPTACLES. PROVIDE CORRECTION. NEC 210.11(C)(1),
 210.52(B); FBC RE E3703.2
 14. PROVIDE ACCURATE LOAD CALCULATION. THE SUM OF LOADS
 PROVIDED IN PANEL SCHEDULE DOES NOT MATCH WHAT IS SHOWN
 AS THE SUM ON THE PLAN. LOAD CALCULATION SHOULD BE IN
 THE FORMAT EXPLAINED IN THE FBC RESIDENTIAL CODE
 LISTED. NEC 220; FBC RE E3602.2
 15. THE WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER
 SPACE STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED
 SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24
 INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET
 IN THAT SPACE AND THAT A RECEPTACLE SHALL BE INSTALLED
 AT EACH WALL COUNTERTOP SPACE THAT IS 12 INCHES OR
 WIDER. THE PLAN PROVIDED DOES NOT MEET THIS CODE IN
 SOME AREAS. PROVIDE CORRECTION. NEC 210.52(C)(1); FBC
 RE E3901.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER