| Date |
Text |
| 2018-06-04 15:54:38 | 06/03/2018 3RD GAS REVIEW **DENIED** |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | PLAN REVIEW IS SUBJECT TO A 4XFEE IF PLANS REVIEW IS |
| | DENIED FOR THE SAME COMMENTS AFTER THE 3RD REVIEW PER |
| | FL ST. STAUTE 553.80 (2B) |
| | |
| | I HAVE PERFORMED A SITE INSPECTION. THERE IS NO |
| | PER-EXISTING GAS LINE FOR THE BBQ AS YOU HAVE TOLD ME |
| | AND AS IN PLAN. THERE IS ALMOST 1 MILLION BTU'S OF GAS |
| | ON THIS HOME AND YOU WILL NEED TO ADDRESS IN FULL ALL |
| | OF THE COMMENT'S. IF YOU REQUIRED ASSISTANCE I WOULD BE |
| | WILLING TO MEET YOU ON-SITE TO HELP SIZE AND LIST |
| | EVERYTHING. |
| | |
| | |
| | 1) PLANS ARE REQUIRED TO HAVE A WET SIGNATURE BY |
| | ENGINEER. DIGITALLY SIGNED PLANS ARE ONLY PERMITTED ON |
| | PLANS THAT HAVE BEEN SUBMITTED DIGITALLY. FLORIDA ADMIN |
| | CODE 61G15-23.001. THE PLAN IS STILL STAMPED DIGITALLY. |
| | |
| | 2) ANSWERED |
| | |
| | 3) THE VALUE OF THIS JOB SEEMS LOW. PROVIDE A BONA FIDE |
| | SIGN CONTRACT TO VERIFY THE TOTAL VALVE, WPB AMEND TO |
| | THE FBC 109.3. YOU MUST WRITE THE TOTAL DIFFERENCE IN |
| | VALUE THAT THE CONTRACT YOU PROVIDED SHOWS. |
| | |
| | 4) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL |
| | GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC. |
| | G2413.4.1, G2413.4.2. |
| | |
| | 5) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1 |
| | |
| | 6) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS |
| | SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) |
| | OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES |
| | G2413.4 (1 ) THROUGH G2413.4 (21). THIS IS NOT THE ONLY |
| | GAS ON THIS SYSTEM. THERE IS ALMOST 1 MILLION BTU'S |
| | EXISTING ON THIS HOUSE. THE SPEC'S PROVIDE FOR THIS |
| | REVIEW LIST THE BBQ AS 60K BUT THE GAS ISOMETRIC ONLY |
| | LIST IT AS 40K |
| | |
| | 7) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR THIS GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. WHAT |
| | YOU PROVIDED DOES NOT LIST ANY APPROVALS |
| | |
| | 8) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL |
| | GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) |
| | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, |
| | G2413.1, G2413.2, & G2413.3. YOU SUBMITTED 2 DIFFERENT |
| | SIZING CHART. WHAT PRESSURE DROP ARE YOU USING AND LIST |
| | WHAT CODE BOOK THIS IS FROM. ALSO YOU WILL NEED TO |
| | INCLUDE THE 2 PSI SIZING CHARTS FOR THE DIFFERENT PIPIE |
| | MATERIAL BEING USED. |
| | |
| | 9) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| | AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS |
| | SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4. |
| | |
| | 10) ) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU |
| | LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE |
| | TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING |
| | SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING |
| | SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING |
| | SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS |
| | THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| | APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| | APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| | PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. |
| | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR |
| | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. |
| | |
| | 11) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC. |
| | G2421.1. |
| | |
| | 12) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE |
| | APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1 |
| | OR 2017 FBC-RES. SEC. G2413.4.1, G2413.4.2 FOR THE |
| | PROPER PIPE SIZE AND BTU LOAD. |
| | |
| | 13) ANSWERED |
| | |
| | 14) ANSWERED |
| | |
| | . |
| | |
| | TIM HUNT |
| | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |
| | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | 561-805-6695 |
| | [email protected] |
| | |
| | |