Plan Review Notes
Plan Review Notes For Permit 18040248
Permit Number 18040248
Review Stop G
Sequence Number 3
Notes
Date Text
2018-06-04 15:54:3806/03/2018 3RD GAS REVIEW **DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 PLAN REVIEW IS SUBJECT TO A 4XFEE IF PLANS REVIEW IS
 DENIED FOR THE SAME COMMENTS AFTER THE 3RD REVIEW PER
 FL ST. STAUTE 553.80 (2B)
  
 I HAVE PERFORMED A SITE INSPECTION. THERE IS NO
 PER-EXISTING GAS LINE FOR THE BBQ AS YOU HAVE TOLD ME
 AND AS IN PLAN. THERE IS ALMOST 1 MILLION BTU'S OF GAS
 ON THIS HOME AND YOU WILL NEED TO ADDRESS IN FULL ALL
 OF THE COMMENT'S. IF YOU REQUIRED ASSISTANCE I WOULD BE
 WILLING TO MEET YOU ON-SITE TO HELP SIZE AND LIST
 EVERYTHING.
  
  
 1) PLANS ARE REQUIRED TO HAVE A WET SIGNATURE BY
 ENGINEER. DIGITALLY SIGNED PLANS ARE ONLY PERMITTED ON
 PLANS THAT HAVE BEEN SUBMITTED DIGITALLY. FLORIDA ADMIN
 CODE 61G15-23.001. THE PLAN IS STILL STAMPED DIGITALLY.
  
 2) ANSWERED
  
 3) THE VALUE OF THIS JOB SEEMS LOW. PROVIDE A BONA FIDE
 SIGN CONTRACT TO VERIFY THE TOTAL VALVE, WPB AMEND TO
 THE FBC 109.3. YOU MUST WRITE THE TOTAL DIFFERENCE IN
 VALUE THAT THE CONTRACT YOU PROVIDED SHOWS.
  
 4) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC.
 G2413.4.1, G2413.4.2.
  
 5) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1
  
 6) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21). THIS IS NOT THE ONLY
 GAS ON THIS SYSTEM. THERE IS ALMOST 1 MILLION BTU'S
 EXISTING ON THIS HOUSE. THE SPEC'S PROVIDE FOR THIS
 REVIEW LIST THE BBQ AS 60K BUT THE GAS ISOMETRIC ONLY
 LIST IT AS 40K
  
 7) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR THIS GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. WHAT
 YOU PROVIDED DOES NOT LIST ANY APPROVALS
  
 8) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3. YOU SUBMITTED 2 DIFFERENT
 SIZING CHART. WHAT PRESSURE DROP ARE YOU USING AND LIST
 WHAT CODE BOOK THIS IS FROM. ALSO YOU WILL NEED TO
 INCLUDE THE 2 PSI SIZING CHARTS FOR THE DIFFERENT PIPIE
 MATERIAL BEING USED.
  
 9) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS
 SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4.
  
 10) ) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 11) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC.
 G2421.1.
  
 12) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1
 OR 2017 FBC-RES. SEC. G2413.4.1, G2413.4.2 FOR THE
 PROPER PIPE SIZE AND BTU LOAD.
  
 13) ANSWERED
  
 14) ANSWERED
  
 .
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  