Plan Review Notes
Plan Review Notes For Permit 18040245
Permit Number 18040245
Review Stop B
Sequence Number 2
Notes
Date Text
2018-06-27 18:15:20****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2017 6TH EDITION
  
 SEE COMMENTS FROM PREVIOUS LIST. A SITE PLAN SHOWING
 LOCATION OF THE AWNING RELATIVE TO THE SIDEWALK AND
 PROPERTY LINE WAS NOT PROVIDED. A DETAIL SHOWING HEIGHT
 OF THE AWNING WAS NOT PROVIDED. NOT ENOUGH INFORMATION
 PROVIDED TO DETERMINE CODE COMPLIANCE.
  
  
 1. RETRACTABLE AWNING.
  
 FBC 3105.3 DESIGN AND CONSTRUCTION.
  
 AWNINGS AND CANOPIES SHALL BE DESIGNED AND CONSTRUCTED
 TO WITHSTAND WIND OR OTHER LATERAL LOADS AND LIVE LOADS
 AS REQUIRED BY CHAPTER 16 AND IN ACCORDANCE WITH
 SECTION 3105.4 OF THIS CODE WITH DUE ALLOWANCE FOR
 SHAPE, OPEN CONSTRUCTION AND SIMILAR FEATURES THAT
 RELIEVE THE PRESSURES OR LOADS. STRUCTURAL MEMBERS
 SHALL BE PROTECTED TO PREVENT DETERIORATION. AWNINGS
 SHALL HAVE FRAMES OF NONCOMBUSTIBLE MATERIAL,
 FIRE-RETARDANT-TREATED WOOD, WOOD OF TYPE IV SIZE, OR
 1-HOUR CONSTRUCTION WITH COMBUSTIBLE OR NONCOMBUSTIBLE
 COVERS AND SHALL BE EITHER FIXED, RETRACTABLE, FOLDING
 OR COLLAPSIBLE.
  
 2. AWNING HEIGHT
  
 PROVIDE DEPTH AND HEIGHT MEASUREMENTS.
 FBC 3105.3.1.4
  
 MOVABLE FABRIC AWNINGS OR FABRIC COVERED FRAMES MAY
 EXTEND OVER PUBLIC PROPERTY FOR A DISTANCE OF NOT MORE
 THAN 5 FEET (1524 MM), PROVIDED SUCH AWNINGS OR ANY
 PART THEREOF MAINTAIN A CLEAR HEIGHT OF 8 FEET (2438
 MM) ABOVE THE SIDEWALK. ALL SUCH MOVABLE AWNINGS SHALL
 BE SUPPORTED ON METAL FRAMES ATTACHED TO THE BUILDING.
  
 3. PROVIDE AWNINGS FABRIC FLAME SPREAD CRITERA.
 FBC 3105.3.4.1
  
 FABRIC USED FOR AWNINGS OR FABRIC-COVERED FRAMES SHALL
 MEET THE FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA
 701 OR HAVE A FLAME SPREAD INDEX NOT GREATER THAN 25
 WHEN TESTED IN ACCORDANCE WITH ASTM E84 OR UL 723.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  
 A THOROUGH REVIEW COULD NOT BE COMPLETED AT THIS TIME,
 AS A RESULT OF THE ADDITIONAL INFORMATION REQUESTED.
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
  
  