| | ****PLAN REVIEW COMMENTS**** |
| | |
| | ART LANGE BUILDING PLANS EXAMINER |
| | |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33402 |
| | 561-805-6718 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE |
| | 2017 6TH EDITION |
| | |
| | 1. RETRACTABLE AWNING. |
| | |
| | FBC 3105.3 DESIGN AND CONSTRUCTION. |
| | |
| | AWNINGS AND CANOPIES SHALL BE DESIGNED AND CONSTRUCTED |
| | TO WITHSTAND WIND OR OTHER LATERAL LOADS AND LIVE LOADS |
| | AS REQUIRED BY CHAPTER 16 AND IN ACCORDANCE WITH |
| | SECTION 3105.4 OF THIS CODE WITH DUE ALLOWANCE FOR |
| | SHAPE, OPEN CONSTRUCTION AND SIMILAR FEATURES THAT |
| | RELIEVE THE PRESSURES OR LOADS. STRUCTURAL MEMBERS |
| | SHALL BE PROTECTED TO PREVENT DETERIORATION. AWNINGS |
| | SHALL HAVE FRAMES OF NONCOMBUSTIBLE MATERIAL, |
| | FIRE-RETARDANT-TREATED WOOD, WOOD OF TYPE IV SIZE, OR |
| | 1-HOUR CONSTRUCTION WITH COMBUSTIBLE OR NONCOMBUSTIBLE |
| | COVERS AND SHALL BE EITHER FIXED, RETRACTABLE, FOLDING |
| | OR COLLAPSIBLE. |
| | |
| | 2. AWNING HEIGHT |
| | |
| | PROVIDE DEPTH AND HEIGHT MEASUREMENTS. |
| | FBC 3105.3.1.4 |
| | |
| | MOVABLE FABRIC AWNINGS OR FABRIC COVERED FRAMES MAY |
| | EXTEND OVER PUBLIC PROPERTY FOR A DISTANCE OF NOT MORE |
| | THAN 5 FEET (1524 MM), PROVIDED SUCH AWNINGS OR ANY |
| | PART THEREOF MAINTAIN A CLEAR HEIGHT OF 8 FEET (2438 |
| | MM) ABOVE THE SIDEWALK. ALL SUCH MOVABLE AWNINGS SHALL |
| | BE SUPPORTED ON METAL FRAMES ATTACHED TO THE BUILDING. |
| | |
| | 3. PROVIDE AWNINGS FABRIC FLAME SPREAD CRITERA. |
| | FBC 3105.3.4.1 |
| | |
| | FABRIC USED FOR AWNINGS OR FABRIC-COVERED FRAMES SHALL |
| | MEET THE FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA |
| | 701 OR HAVE A FLAME SPREAD INDEX NOT GREATER THAN 25 |
| | WHEN TESTED IN ACCORDANCE WITH ASTM E84 OR UL 723. |
| | |
| | |
| | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2 |
| | 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. |
| | |
| | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED |
| | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS |
| | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE |
| | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE |
| | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR |
| | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN |
| | THE PERMIT PACKAGE. |
| | |
| | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS |
| | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. |
| | |
| | A THOROUGH REVIEW COULD NOT BE COMPLETED AT THIS TIME, |
| | AS A RESULT OF THE ADDITIONAL INFORMATION REQUESTED. |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | |
| | |
| | |