| 2018-07-12 10:40:57 | 2ND REVIEW: FBC 2017 6TH EDITION |
| | |
| | PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED WITH. |
| | |
| | 1. THE BUILDING SHALL COMPLY WITH THE FAIR HOUSING ACT. |
| | C) PROVIDE DETAILS THAT SHOW THE MOUNTING HEIGHTS FOR |
| | THE GRAB BAR BACKING. PER FHA REQUIREMENT #6 THE GRAB |
| | BAR BACKING FOR THE TOILET SHALL COMPLY WITH FIG. #3 IN |
| | THE FHA GUIDELINES AND THE SHOWER FIG. #5 |
| | |
| | 2. PROVIDE A PLUMBING FLOOR PLAN WITH PIPING AND SITE |
| | PLAN. PER WPB AMEND TO FBC 107.3.5.1.3 |
| | |
| | 3. PROVIDE WATER ISOMETRIC DRAWING. PER WPB AMEND TO |
| | FBC 107.3.5.1.3(13) |
| | |
| | 4. PROVIDE DETAIL FOR WATER HEATER PIPING. PER WPB |
| | AMEND TO FBC 107.3.5.1.3(5) |
| | |
| | NEW COMMENTS: |
| | |
| | 1. SHT. A-6 THE BACKING FOR THE GRAB BARS IS NOT SHOWN |
| | BEHIND THE TOILET ON THE DETAIL FOR TYPE B BATHEOOM. |
| | PLEASE SHOW PER FHA REQUIREMENT #6 |
| | |
| | 2. SHT.S-3 ON THE SANITARY RISER FOR THE LAUNDRY, THE |
| | LAUNDRY SINK WASTE ARM SHALL CONNECT TO THE WASTE STACK |
| | SEPARATELY FROM THE WASHING MACHINE. PER FBC PL 901.2.1 |
| | |
| | 3. THIS 4 UNIT BUILDING IT IS A MULTI FAMILY AND FALLS |
| | UNDER THE FBC NOT THE FBC RESIDENTIAL ON SHT. CS UNDER |
| | CODE COMPLIANCE AND GENERAL ARCHITECTURAL NOTES AND |
| | SHT. S-3 UNDER PLUMBING NOTES IT REFERENCES THR |
| | RESIDENTIAL CODE PLEASE REMOVE ANY REFERENCES TO THE |
| | RESIDENTIAL CODE. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |