Plan Review Notes
Plan Review Notes For Permit 18040194
Permit Number 18040194
Review Stop E
Sequence Number 1
Notes
Date Text
2018-05-01 10:56:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 2. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANELS.
 NEC 110.3, 110.9
 3. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 4. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 5. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE
 CORRECTION. NEC 210.11(C)(3)
 6. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94
 7. SHOW LOCATION OF SERVICE EQUIPMENT ON PLAN. FBC
 107.2.1
 8. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER
 CODE. NEC 210.64
 9. ONLY RECEPTACLE OUTLETS ARE SHOWN AS AFCI PROTECTED
 ON PLAN. PER CODE, ALL BRANCH CIRCUITS THAT SUPPLY
 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS
 INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS,
 LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI
 PROTECTED. PROVIDE CORRECTION. NEC 210.12; FBC RE
 E3902.16
 10. PROVIDE LOAD CALCULATION FOR SERVICE TO CONFIRM
 CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30
 11. PROVIDE ADDRESS OF PROJECT ON PLAN. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  