2018-06-30 13:14:1306/30/2018 3ND PLUMBING REVIEW**DENIED**
  
 NOTE: A 4X PLAN REVIEW FEE WILL BE ADDED IF PLANS ARE
 REJECTED AGAIN. FL ST. STAUTE 553.80 (2B)
  
 NOT ALL COMMENTS HAVE BE ADDRESS
  
 1) OK
  
 2) AS AN R-3 OCCUPANCY AN AUTOMATIC CLOTHS WASHER IS
 REQUIRED IN EACH UNIT. FBC-P 403.1 BOTH FLOOR PLAN NOR
 PLUMBING ISOMETRIC SHOW SUCH.
  
 3) OK
  
 4) YOU HAVE CHANGES THE WATER HEATER FROM 100 GALLONS
 TO A 30 GALLON IN EACH UNIT BUT THE E.F RATING IS SHOWN
 AS .93. AGAIN AS OF APRIL 16,2016 THE MIN E.F ALLOWED
 IS .95. PLEASE REFER TO THE CODE OF FEDERAL REGULATION
 (CFR) 75 FR 200112**DOE 10 CRF PART 430.
  
 5) PLAN IS SHOWING CLEAR FLOOR SPACING REFERING TO FAIR
 HOUSING, IS IT YOUR INTENT TO FULLY COMPLY WITH FHA?
 FBC 107.2.1
  
 6) SHOW WATER HEATER PIPING DETAIL IN REGARDS TO THE
 DISCHARGE PIPING FROM THE RELIEF LINE INTO THE PAN AND
 THE PAN DRAIN DISCHARGING OUTSIDE OF THE DWELLING.
 FBC-P 2801.6, 2801.6.1
  
 IT IS HELPFUL TO PROVIDE A NARRATIVE TO THE COMMENTS.
  