| Plan Review Notes For Permit 18040193 |
| Permit Number |
18040193 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-06-30 13:14:13 | 06/30/2018 3ND PLUMBING REVIEW**DENIED** | | | | | | NOTE: A 4X PLAN REVIEW FEE WILL BE ADDED IF PLANS ARE | | | REJECTED AGAIN. FL ST. STAUTE 553.80 (2B) | | | | | | NOT ALL COMMENTS HAVE BE ADDRESS | | | | | | 1) OK | | | | | | 2) AS AN R-3 OCCUPANCY AN AUTOMATIC CLOTHS WASHER IS | | | REQUIRED IN EACH UNIT. FBC-P 403.1 BOTH FLOOR PLAN NOR | | | PLUMBING ISOMETRIC SHOW SUCH. | | | | | | 3) OK | | | | | | 4) YOU HAVE CHANGES THE WATER HEATER FROM 100 GALLONS | | | TO A 30 GALLON IN EACH UNIT BUT THE E.F RATING IS SHOWN | | | AS .93. AGAIN AS OF APRIL 16,2016 THE MIN E.F ALLOWED | | | IS .95. PLEASE REFER TO THE CODE OF FEDERAL REGULATION | | | (CFR) 75 FR 200112**DOE 10 CRF PART 430. | | | | | | 5) PLAN IS SHOWING CLEAR FLOOR SPACING REFERING TO FAIR | | | HOUSING, IS IT YOUR INTENT TO FULLY COMPLY WITH FHA? | | | FBC 107.2.1 | | | | | | 6) SHOW WATER HEATER PIPING DETAIL IN REGARDS TO THE | | | DISCHARGE PIPING FROM THE RELIEF LINE INTO THE PAN AND | | | THE PAN DRAIN DISCHARGING OUTSIDE OF THE DWELLING. | | | FBC-P 2801.6, 2801.6.1 | | | | | | IT IS HELPFUL TO PROVIDE A NARRATIVE TO THE COMMENTS. | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | | | | |
|