| 2018-04-17 15:51:01 | 04/17/2018 2ND PLUMBING REVIEW**DENIED**1ST REVIEW |
| | RESCINDED** |
| | |
| | 1) COVER SHEET INFORMATION BLOCK LIST OCCUPANCY AS R-3 |
| | BUT UNDER COMPLIANCE REQUIREMENTS OCCUPANCY IS LISTED |
| | AS R-2. PER FBC-P SECTION 403.1 BEING THIS BUILDING IS |
| | LESS THEN 3 UNITS IT WOULD BE CLASSIFIED AS R-3 |
| | |
| | 2) AS AN R-3 OCCUPANCY AN AUTOMATIC CLOTHS IS REQUIRED |
| | IN EACH UNIT. FBC-P 403.1 |
| | |
| | 3) THE ADDRESS DOES NOT APPEAR ON THE PLAN. FBC 107.2.1 |
| | |
| | 4) THE FLORIDA ENERGY FORM R405-2017 LIST THE WATER |
| | HEATER'S AS 100 GALLON .91 E.F. RESIDENTIAL WATER |
| | HEATER'S MANUFACTURED AFTER APRIL 16, 2015 ARE |
| | PERMITTED TO BE MAX 55 GALLON WITH A MIN E.F OF .95 |
| | UNLESS THE HEATER IS OF HEAT PUMP TECHNOLOGY THEN THE |
| | MIN E.F (LARGER THEN 55 GALLON) WOULD THEN BE 1.98E.F. |
| | FBC- EFFICIENCY CONSERVATION R403.5.6.2 AND DEFINED IN |
| | THE |
| | CODE OF FEDERAL REGULATION ( CFR) 75 FR 2012. |
| | |
| | 5) THE BATHROOMS ARE SHOWING AS HAVING ACCESSIBILITY |
| | COMPLAINT CLEAR FLOOR SPACES AND ROLL IN SHOWERS. IS IT |
| | YOUR INTENT TO FULLY COMPLY WITH THE FLORIDA |
| | ACCESSIBILITY CODE IN FULL? FBC 107.2.1 |
| | |
| | 6) SHOW WATER HEATER DETAIL IN REGARDS TO THE PIPING |
| | FOR THE REQUIRED PAN DRAIN AND DISCHARGING OF THE |
| | RELIEF LINE INTO THE ROOM. FBC-P 2801.6, 2801.6.1, |
| | 2804.6.1 |
| | |
| | 7) BOTH UNIT AS LISTED AS UNIT # A. PLEASE CORRECT |
| | SHOWING THE 2ND UNIT AS DIFFERENT |
| | |
| | TIM HUNT |
| | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |
| | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | 561-805-6695 |
| | [email protected] |
| | |