Plan Review Notes
Plan Review Notes For Permit 18040193
Permit Number 18040193
Review Stop P
Sequence Number 2
Notes
Date Text
2018-04-17 15:51:0104/17/2018 2ND PLUMBING REVIEW**DENIED**1ST REVIEW
 RESCINDED**
  
 1) COVER SHEET INFORMATION BLOCK LIST OCCUPANCY AS R-3
 BUT UNDER COMPLIANCE REQUIREMENTS OCCUPANCY IS LISTED
 AS R-2. PER FBC-P SECTION 403.1 BEING THIS BUILDING IS
 LESS THEN 3 UNITS IT WOULD BE CLASSIFIED AS R-3
  
 2) AS AN R-3 OCCUPANCY AN AUTOMATIC CLOTHS IS REQUIRED
 IN EACH UNIT. FBC-P 403.1
  
 3) THE ADDRESS DOES NOT APPEAR ON THE PLAN. FBC 107.2.1
  
 4) THE FLORIDA ENERGY FORM R405-2017 LIST THE WATER
 HEATER'S AS 100 GALLON .91 E.F. RESIDENTIAL WATER
 HEATER'S MANUFACTURED AFTER APRIL 16, 2015 ARE
 PERMITTED TO BE MAX 55 GALLON WITH A MIN E.F OF .95
 UNLESS THE HEATER IS OF HEAT PUMP TECHNOLOGY THEN THE
 MIN E.F (LARGER THEN 55 GALLON) WOULD THEN BE 1.98E.F.
 FBC- EFFICIENCY CONSERVATION R403.5.6.2 AND DEFINED IN
 THE
 CODE OF FEDERAL REGULATION ( CFR) 75 FR 2012.
  
 5) THE BATHROOMS ARE SHOWING AS HAVING ACCESSIBILITY
 COMPLAINT CLEAR FLOOR SPACES AND ROLL IN SHOWERS. IS IT
 YOUR INTENT TO FULLY COMPLY WITH THE FLORIDA
 ACCESSIBILITY CODE IN FULL? FBC 107.2.1
  
 6) SHOW WATER HEATER DETAIL IN REGARDS TO THE PIPING
 FOR THE REQUIRED PAN DRAIN AND DISCHARGING OF THE
 RELIEF LINE INTO THE ROOM. FBC-P 2801.6, 2801.6.1,
 2804.6.1
  
 7) BOTH UNIT AS LISTED AS UNIT # A. PLEASE CORRECT
 SHOWING THE 2ND UNIT AS DIFFERENT
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  