| 2018-07-07 11:03:45 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18040193 |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. OK |
| | |
| | 2. OK |
| | |
| | 3. NOT ADDRESSED. ON SHEET A-1, THE B-B CROSS SECTION |
| | IS MIS-LABELED AS BEING ON SHEET A-4. PLEASE CORRECT |
| | FBC 107.2.1 |
| | |
| | 4. OK |
| | |
| | 5. OK |
| | |
| | 6. PARTIALLY ADDRESSED. PLEASE ADD VESTIBULE ATTIC |
| | ACCESS TO SHEET S-4. |
| | |
| | 7. OK |
| | |
| | 8. OK |
| | |
| | 9. IS THIS FIBERGLASS DOOR BEING USED(FL20468.4)? |
| | IT LOOKS LIKE IT WAS BEING SUBMITTED AS THE VESTIBULE |
| | ENTRY DOORS. THOSE DOORS SHOW ON PLAN A-1 AS 1 HR FIRE |
| | RATED TO MAINTAIN THE FIRE WALL SEPARATION. |
| | |
| | 10. OK |
| | |
| | 11. UPDATE N.O.A. FOR WINDOWS ON SHEET A-2(M-D NOA |
| | 0630.08) TO MATCH THE NOA PROVIDED(NOA #16-0714.06) |
| | |
| | 12. OK |
| | |
| | 13. NOT PROVIDED - IN ORDER TO REDUCE PLAN REVIEW TIME, |
| | PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH OF |
| | THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| | |
| | 14. [NEW COMMENT] ON SHEET S-4 KEYNOTE #3 HAS WALL |
| | U465. WHERE ON THE PLANS DOES THIS WALL GET INSTALLED? |
| | ADD NOTE TO PLANS TO SHOW WHERE THIS WALL IS INSTALLED. |
| | IT LOOKS LIKE IT WOULD BE INFILL TO FINISH WHERE THERE |
| | ARE NO RAKE BEAMS. |
| | PLEASE LOOK AT SECTION [FBC R-302.3] TWO FAMILY |
| | DWELLING. THIS IS WHAT WOULD APPLY FOR SEPARATION OF |
| | THESE UNITS. |
| | |
| | NOTE: |
| | ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | PLEASE PROVIDE TWO IDENTICAL COPIES OF ALL ITEMS |
| | SUBMITTED. |
| | |