| 2018-05-21 13:38:11 | PERMIT # 18040171 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | FAILED COMMENTS: |
| | |
| | 1) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE |
| | COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION |
| | SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS |
| | MAY BE GENERATED DURING PLAN RESUBMISSION. |
| | |
| | 2) A COMPLETE SYSTEMS AND DEVICE LAYOUT PLAN IS NOT |
| | PROVIDED. |
| | |
| | 3) PER NFPA 2001, CHAPTER 5, THE FOLLOWING DETAILS ARE |
| | REQUIRED AS PART OF THE PLAN REVIEW SUBMITTAL: |
| | |
| | 5.1.2: WORKING PLANS |
| | 5.1.2.1 |
| | WORKING PLANS AND CALCULATIONS SHALL BE SUBMITTED FOR |
| | APPROVAL TO THE AUTHORITY HAVING JURISDICTION BEFORE |
| | SYSTEM INSTALLATION OR REMODELING BEGINS. THESE |
| | DOCUMENTS SHALL BE PREPARED ONLY BY PERSONS FULLY |
| | EXPERIENCED AND QUALIFIED IN THE DESIGN OF TOTAL |
| | FLOODING AND LOCAL APPLICATION CLEAN AGENT FIRE |
| | EXTINGUISHING SYSTEMS. DEVIATION FROM THESE DOCUMENTS |
| | SHALL REQUIRE PERMISSION OF THE AUTHORITY HAVING |
| | JURISDICTION. |
| | |
| | 5.1.2.2 |
| | WORKING PLANS SHALL BE DRAWN TO AN INDICATED SCALE AND |
| | SHALL SHOW THE FOLLOWING ITEMS THAT PERTAIN TO THE |
| | DESIGN OF THE SYSTEM: |
| | (1) NAME OF OWNER AND OCCUPANT |
| | (2) LOCATION, INCLUDING STREET ADDRESS |
| | (3) POINT OF COMPASS AND SYMBOL LEGEND |
| | (4) LOCATION AND CONSTRUCTION OF PROTECTED ENCLOSURE |
| | WALLS AND PARTITIONS |
| | (5) LOCATION OF FIRE WALLS |
| | (6) ENCLOSURE CROSS SECTION, SHOWN AS A FULL-HEIGHT OR |
| | SCHEMATIC DIAGRAM, INCLUDING LOCATION AND CONSTRUCTION |
| | OF BUILDING FLOOR-CEILING ASSEMBLIES ABOVE AND BELOW, |
| | RAISED ACCESS FLOOR, AND SUSPENDED CEILING |
| | (7) AGENT BEING USED |
| | (8) AGENT CONCENTRATION AT THE LOWEST TEMPERATURE AND |
| | THE HIGHEST TEMPERATURE FOR WHICH THE ENCLOSURE IS |
| | PROTECTED |
| | (9) DESCRIPTION OF OCCUPANCIES AND HAZARDS BEING |
| | PROTECTED, DESIGNATING WHETHER THE ENCLOSURE IS |
| | NORMALLY OCCUPIED |
| | (10) FOR AN ENCLOSURE PROTECTED BY A CLEAN AGENT FIRE |
| | EXTINGUISHING SYSTEM, AN ESTIMATE OF THE MAXIMUM |
| | POSITIVE PRESSURE AND THE MAXIMUM NEGATIVE PRESSURE, |
| | RELATIVE TO AMBIENT PRESSURE, EXPECTED TO BE DEVELOPED |
| | UPON THE DISCHARGE OF AGENT |
| | (11) DESCRIPTION OF EXPOSURES SURROUNDING THE ENCLOSURE |
| | (12) DESCRIPTION OF THE AGENT STORAGE CONTAINERS USED, |
| | INCLUDING INTERNAL VOLUME, STORAGE PRESSURE, AND |
| | NOMINAL CAPACITY EXPRESSED IN UNITS OF AGENT MASS OR |
| | VOLUME AT STANDARD CONDITIONS OF TEMPERATURE AND |
| | PRESSURE |
| | (13) DESCRIPTION OF NOZZLE(S) USED, INCLUDING SIZE, |
| | ORIFICE PORT CONFIGURATION, AND EQUIVALENT ORIFICE AREA |
| | (14) DESCRIPTION OF PIPE AND FITTINGS USED, INCLUDING |
| | MATERIAL SPECIFICATIONS, GRADE, AND PRESSURE RATING |
| | (15) DESCRIPTION OF WIRE OR CABLE USED, INCLUDING |
| | CLASSIFICATION, GAUGE [AMERICAN WIRE GAUGE (AWG)], |
| | SHIELDING, NUMBER OF STRANDS IN CONDUCTOR, CONDUCTOR |
| | MATERIAL, AND COLOR CODING SCHEDULE; SEGREGATION |
| | REQUIREMENTS OF VARIOUS SYSTEM CONDUCTORS; AND REQUIRED |
| | METHOD OF MAKING WIRE TERMINATIONS |
| | (16) DESCRIPTION OF THE METHOD OF DETECTOR MOUNTING |
| | (17) EQUIPMENT SCHEDULE OR BILL OF MATERIALS FOR EACH |
| | PIECE OF EQUIPMENT OR DEVICE SHOWING DEVICE NAME, |
| | MANUFACTURER, MODEL OR PART NUMBER, QUANTITY, AND |
| | DESCRIPTION |
| | (18) PLAN VIEW OF PROTECTED AREA SHOWING ENCLOSURE |
| | PARTITIONS (FULL AND PARTIAL HEIGHT); AGENT |
| | DISTRIBUTION SYSTEM, INCLUDING AGENT STORAGE |
| | CONTAINERS, PIPING, AND NOZZLES; TYPE OF PIPE HANGERS |
| | AND RIGID PIPE SUPPORTS; DETECTION, ALARM, AND CONTROL |
| | SYSTEM, INCLUDING ALL DEVICES AND SCHEMATIC OF WIRING |
| | INTERCONNECTION BETWEEN THEM; END-OF-LINE DEVICE |
| | LOCATIONS; LOCATION OF CONTROLLED DEVICES SUCH AS |
| | DAMPERS AND SHUTTERS; AND LOCATION OF INSTRUCTIONAL |
| | SIGNAGE |
| | (19) ISOMETRIC VIEW OF AGENT DISTRIBUTION SYSTEM |
| | SHOWING THE LENGTH AND DIAMETER OF EACH PIPE SEGMENT; |
| | NODE REFERENCE NUMBERS RELATING TO THE FLOW |
| | CALCULATIONS; FITTINGS, INCLUDING REDUCERS, STRAINERS, |
| | AND ORIENTATION OF TEES; AND NOZZLES, INCLUDING SIZE, |
| | ORIFICE PORT CONFIGURATION, FLOW RATE, AND EQUIVALENT |
| | ORIFICE AREA |
| | (20) SCALE DRAWING SHOWING THE LAYOUT OF THE |
| | ANNUNCIATOR PANEL GRAPHICS IF REQUIRED BY THE AUTHORITY |
| | HAVING JURISDICTION |
| | (21) DETAILS OF EACH UNIQUE RIGID PIPE SUPPORT |
| | CONFIGURATION SHOWING METHOD OF SECUREMENT TO THE PIPE |
| | AND TO THE BUILDING STRUCTURE |
| | (22) DETAILS OF THE METHOD OF CONTAINER SECUREMENT |
| | SHOWING METHOD OF SECUREMENT TO THE CONTAINER AND TO |
| | THE BUILDING STRUCTURE |
| | (23) COMPLETE STEP-BY-STEP DESCRIPTION OF THE SYSTEM |
| | SEQUENCE OF OPERATIONS, INCLUDING FUNCTIONING OF ABORT |
| | AND MAINTENANCE SWITCHES, DELAY TIMERS, AND EMERGENCY |
| | POWER SHUTDOWN |
| | (24) POINT-TO-POINT WIRING SCHEMATIC DIAGRAMS SHOWING |
| | ALL CIRCUIT CONNECTIONS TO THE SYSTEM CONTROL PANEL AND |
| | GRAPHIC ANNUNCIATOR PANEL |
| | (25) POINT-TO-POINT WIRING SCHEMATIC DIAGRAMS SHOWING |
| | ALL CIRCUIT CONNECTIONS TO EXTERNAL OR ADD-ON RELAYS |
| | (26) COMPLETE CALCULATIONS TO DETERMINE ENCLOSURE |
| | VOLUME, QUANTITY OF CLEAN AGENT, AND SIZE OF BACKUP |
| | BATTERIES; METHOD USED TO DETERMINE NUMBER AND LOCATION |
| | OF AUDIBLE AND VISUAL INDICATING DEVICES; AND NUMBER |
| | AND LOCATION OF DETECTORS |
| | (27) DETAILS OF ANY SPECIAL FEATURES |
| | (28) *PRESSURE RELIEF VENT AREA, OR EQUIVALENT LEAKAGE |
| | AREA, FOR THE PROTECTED ENCLOSURE TO PREVENT |
| | DEVELOPMENT, DURING SYSTEM DISCHARGE, OF A PRESSURE |
| | DIFFERENCE ACROSS THE ENCLOSURE BOUNDARIES THAT EXCEEDS |
| | A SPECIFIED ENCLOSURE PRESSURE LIMIT |
| | |
| | 5.1.2.3 |
| | THE DETAIL ON THE SYSTEM SHALL INCLUDE INFORMATION AND |
| | CALCULATIONS ON THE QUANTITY OF AGENT; CONTAINER |
| | STORAGE PRESSURE; INTERNAL VOLUME OF THE CONTAINER; THE |
| | LOCATION, TYPE, AND FLOW RATE OF EACH NOZZLE, INCLUDING |
| | EQUIVALENT ORIFICE AREA; THE LOCATION, SIZE, AND |
| | EQUIVALENT LENGTHS OF PIPE, FITTINGS, AND HOSE; AND THE |
| | LOCATION AND SIZE OF THE STORAGE FACILITY. PIPE SIZE |
| | REDUCTION AND ORIENTATION OF TEES SHALL BE CLEARLY |
| | INDICATED. INFORMATION SHALL BE SUBMITTED PERTAINING TO |
| | THE LOCATION AND FUNCTION OF THE DETECTION DEVICES, |
| | OPERATING DEVICES, AUXILIARY EQUIPMENT, AND ELECTRICAL |
| | CIRCUITRY, IF USED. APPARATUS AND DEVICES USED SHALL BE |
| | IDENTIFIED. ANY SPECIAL FEATURES SHALL BE ADEQUATELY |
| | EXPLAINED. |
| | |
| | 5.1.2.3.1 |
| | PRE-ENGINEERED SYSTEMS SHALL NOT BE REQUIRED TO SPECIFY |
| | AN INTERNAL VOLUME OF THE CONTAINER, NOZZLE FLOW RATES, |
| | EQUIVALENT LENGTHS OF PIPE, FITTINGS, AND HOSE, OR FLOW |
| | CALCULATIONS, WHEN USED WITHIN THEIR LISTED |
| | LIMITATIONS. THE INFORMATION REQUIRED BY THE LISTED |
| | SYSTEM DESIGN MANUAL, HOWEVER, SHALL BE MADE AVAILABLE |
| | TO THE AUTHORITY HAVING JURISDICTION FOR VERIFICATION |
| | THAT THE SYSTEM IS WITHIN ITS LISTED LIMITATIONS. |
| | |
| | 5.1.2.4 |
| | AN ?AS-BUILT? INSTRUCTION AND MAINTENANCE MANUAL THAT |
| | INCLUDES A FULL SEQUENCE OF OPERATIONS AND A FULL SET |
| | OF DRAWINGS AND CALCULATIONS SHALL BE MAINTAINED ON |
| | SITE. |
| | |
| | 5.1.2.5 FLOW CALCULATIONS. |
| | 5.1.2.5.1 |
| | FLOW CALCULATIONS ALONG WITH THE WORKING PLANS SHALL BE |
| | SUBMITTED TO THE AUTHORITY HAVING JURISDICTION FOR |
| | APPROVAL. THE VERSION OF THE FLOW CALCULATION PROGRAM |
| | SHALL BE IDENTIFIED ON THE COMPUTER CALCULATION |
| | PRINTOUT. |
| | |
| | 5.1.2.5.2 |
| | WHERE FIELD CONDITIONS NECESSITATE ANY MATERIAL CHANGE |
| | FROM APPROVED PLANS, THE CHANGE SHALL BE SUBMITTED FOR |
| | APPROVAL. |
| | |
| | 5.1.2.5.3 |
| | WHEN SUCH MATERIAL CHANGES FROM APPROVED PLANS ARE |
| | MADE, CORRECTED ?AS-INSTALLED? PLANS SHALL BE PROVIDED. |
| | |
| | 5.1.3 APPROVAL OF PLANS. |
| | 5.1.3.1 |
| | PLANS AND CALCULATIONS SHALL BE APPROVED PRIOR TO |
| | INSTALLATION. |
| | |
| | 4) IS THIS BUILDING EQUIPPED WITH A COMPLETE AND FULLY |
| | FUNCTIONAL FIRE SPRINKLER SYSTEM? IF SO, PLEASE PROVIDE |
| | LAYOUT OF THE FIRE SPRINKLER SYSTEM IN RELATION TO THE |
| | CLEAN AGENT SYSTEM BEING INSTALLED. |
| | |
| | |
| | |
| | SUE ELLEN CALDERON |
| | ASSISTANT FIRE MARSHAL |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 804-4751 |
| | |
| | |
| | |
| | |