2018-05-21 13:38:11PERMIT # 18040171
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION
 SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED DURING PLAN RESUBMISSION.
  
 2) A COMPLETE SYSTEMS AND DEVICE LAYOUT PLAN IS NOT
 PROVIDED.
  
 3) PER NFPA 2001, CHAPTER 5, THE FOLLOWING DETAILS ARE
 REQUIRED AS PART OF THE PLAN REVIEW SUBMITTAL:
  
 5.1.2: WORKING PLANS
 5.1.2.1
 WORKING PLANS AND CALCULATIONS SHALL BE SUBMITTED FOR
 APPROVAL TO THE AUTHORITY HAVING JURISDICTION BEFORE
 SYSTEM INSTALLATION OR REMODELING BEGINS. THESE
 DOCUMENTS SHALL BE PREPARED ONLY BY PERSONS FULLY
 EXPERIENCED AND QUALIFIED IN THE DESIGN OF TOTAL
 FLOODING AND LOCAL APPLICATION CLEAN AGENT FIRE
 EXTINGUISHING SYSTEMS. DEVIATION FROM THESE DOCUMENTS
 SHALL REQUIRE PERMISSION OF THE AUTHORITY HAVING
 JURISDICTION.
  
 5.1.2.2
 WORKING PLANS SHALL BE DRAWN TO AN INDICATED SCALE AND
 SHALL SHOW THE FOLLOWING ITEMS THAT PERTAIN TO THE
 DESIGN OF THE SYSTEM:
 (1) NAME OF OWNER AND OCCUPANT
 (2) LOCATION, INCLUDING STREET ADDRESS
 (3) POINT OF COMPASS AND SYMBOL LEGEND
 (4) LOCATION AND CONSTRUCTION OF PROTECTED ENCLOSURE
 WALLS AND PARTITIONS
 (5) LOCATION OF FIRE WALLS
 (6) ENCLOSURE CROSS SECTION, SHOWN AS A FULL-HEIGHT OR
 SCHEMATIC DIAGRAM, INCLUDING LOCATION AND CONSTRUCTION
 OF BUILDING FLOOR-CEILING ASSEMBLIES ABOVE AND BELOW,
 RAISED ACCESS FLOOR, AND SUSPENDED CEILING
 (7) AGENT BEING USED
 (8) AGENT CONCENTRATION AT THE LOWEST TEMPERATURE AND
 THE HIGHEST TEMPERATURE FOR WHICH THE ENCLOSURE IS
 PROTECTED
 (9) DESCRIPTION OF OCCUPANCIES AND HAZARDS BEING
 PROTECTED, DESIGNATING WHETHER THE ENCLOSURE IS
 NORMALLY OCCUPIED
 (10) FOR AN ENCLOSURE PROTECTED BY A CLEAN AGENT FIRE
 EXTINGUISHING SYSTEM, AN ESTIMATE OF THE MAXIMUM
 POSITIVE PRESSURE AND THE MAXIMUM NEGATIVE PRESSURE,
 RELATIVE TO AMBIENT PRESSURE, EXPECTED TO BE DEVELOPED
 UPON THE DISCHARGE OF AGENT
 (11) DESCRIPTION OF EXPOSURES SURROUNDING THE ENCLOSURE
 (12) DESCRIPTION OF THE AGENT STORAGE CONTAINERS USED,
 INCLUDING INTERNAL VOLUME, STORAGE PRESSURE, AND
 NOMINAL CAPACITY EXPRESSED IN UNITS OF AGENT MASS OR
 VOLUME AT STANDARD CONDITIONS OF TEMPERATURE AND
 PRESSURE
 (13) DESCRIPTION OF NOZZLE(S) USED, INCLUDING SIZE,
 ORIFICE PORT CONFIGURATION, AND EQUIVALENT ORIFICE AREA
 (14) DESCRIPTION OF PIPE AND FITTINGS USED, INCLUDING
 MATERIAL SPECIFICATIONS, GRADE, AND PRESSURE RATING
 (15) DESCRIPTION OF WIRE OR CABLE USED, INCLUDING
 CLASSIFICATION, GAUGE [AMERICAN WIRE GAUGE (AWG)],
 SHIELDING, NUMBER OF STRANDS IN CONDUCTOR, CONDUCTOR
 MATERIAL, AND COLOR CODING SCHEDULE; SEGREGATION
 REQUIREMENTS OF VARIOUS SYSTEM CONDUCTORS; AND REQUIRED
 METHOD OF MAKING WIRE TERMINATIONS
 (16) DESCRIPTION OF THE METHOD OF DETECTOR MOUNTING
 (17) EQUIPMENT SCHEDULE OR BILL OF MATERIALS FOR EACH
 PIECE OF EQUIPMENT OR DEVICE SHOWING DEVICE NAME,
 MANUFACTURER, MODEL OR PART NUMBER, QUANTITY, AND
 DESCRIPTION
 (18) PLAN VIEW OF PROTECTED AREA SHOWING ENCLOSURE
 PARTITIONS (FULL AND PARTIAL HEIGHT); AGENT
 DISTRIBUTION SYSTEM, INCLUDING AGENT STORAGE
 CONTAINERS, PIPING, AND NOZZLES; TYPE OF PIPE HANGERS
 AND RIGID PIPE SUPPORTS; DETECTION, ALARM, AND CONTROL
 SYSTEM, INCLUDING ALL DEVICES AND SCHEMATIC OF WIRING
 INTERCONNECTION BETWEEN THEM; END-OF-LINE DEVICE
 LOCATIONS; LOCATION OF CONTROLLED DEVICES SUCH AS
 DAMPERS AND SHUTTERS; AND LOCATION OF INSTRUCTIONAL
 SIGNAGE
 (19) ISOMETRIC VIEW OF AGENT DISTRIBUTION SYSTEM
 SHOWING THE LENGTH AND DIAMETER OF EACH PIPE SEGMENT;
 NODE REFERENCE NUMBERS RELATING TO THE FLOW
 CALCULATIONS; FITTINGS, INCLUDING REDUCERS, STRAINERS,
 AND ORIENTATION OF TEES; AND NOZZLES, INCLUDING SIZE,
 ORIFICE PORT CONFIGURATION, FLOW RATE, AND EQUIVALENT
 ORIFICE AREA
 (20) SCALE DRAWING SHOWING THE LAYOUT OF THE
 ANNUNCIATOR PANEL GRAPHICS IF REQUIRED BY THE AUTHORITY
 HAVING JURISDICTION
 (21) DETAILS OF EACH UNIQUE RIGID PIPE SUPPORT
 CONFIGURATION SHOWING METHOD OF SECUREMENT TO THE PIPE
 AND TO THE BUILDING STRUCTURE
 (22) DETAILS OF THE METHOD OF CONTAINER SECUREMENT
 SHOWING METHOD OF SECUREMENT TO THE CONTAINER AND TO
 THE BUILDING STRUCTURE
 (23) COMPLETE STEP-BY-STEP DESCRIPTION OF THE SYSTEM
 SEQUENCE OF OPERATIONS, INCLUDING FUNCTIONING OF ABORT
 AND MAINTENANCE SWITCHES, DELAY TIMERS, AND EMERGENCY
 POWER SHUTDOWN
 (24) POINT-TO-POINT WIRING SCHEMATIC DIAGRAMS SHOWING
 ALL CIRCUIT CONNECTIONS TO THE SYSTEM CONTROL PANEL AND
 GRAPHIC ANNUNCIATOR PANEL
 (25) POINT-TO-POINT WIRING SCHEMATIC DIAGRAMS SHOWING
 ALL CIRCUIT CONNECTIONS TO EXTERNAL OR ADD-ON RELAYS
 (26) COMPLETE CALCULATIONS TO DETERMINE ENCLOSURE
 VOLUME, QUANTITY OF CLEAN AGENT, AND SIZE OF BACKUP
 BATTERIES; METHOD USED TO DETERMINE NUMBER AND LOCATION
 OF AUDIBLE AND VISUAL INDICATING DEVICES; AND NUMBER
 AND LOCATION OF DETECTORS
 (27) DETAILS OF ANY SPECIAL FEATURES
 (28) *PRESSURE RELIEF VENT AREA, OR EQUIVALENT LEAKAGE
 AREA, FOR THE PROTECTED ENCLOSURE TO PREVENT
 DEVELOPMENT, DURING SYSTEM DISCHARGE, OF A PRESSURE
 DIFFERENCE ACROSS THE ENCLOSURE BOUNDARIES THAT EXCEEDS
 A SPECIFIED ENCLOSURE PRESSURE LIMIT
  
 5.1.2.3
 THE DETAIL ON THE SYSTEM SHALL INCLUDE INFORMATION AND
 CALCULATIONS ON THE QUANTITY OF AGENT; CONTAINER
 STORAGE PRESSURE; INTERNAL VOLUME OF THE CONTAINER; THE
 LOCATION, TYPE, AND FLOW RATE OF EACH NOZZLE, INCLUDING
 EQUIVALENT ORIFICE AREA; THE LOCATION, SIZE, AND
 EQUIVALENT LENGTHS OF PIPE, FITTINGS, AND HOSE; AND THE
 LOCATION AND SIZE OF THE STORAGE FACILITY. PIPE SIZE
 REDUCTION AND ORIENTATION OF TEES SHALL BE CLEARLY
 INDICATED. INFORMATION SHALL BE SUBMITTED PERTAINING TO
 THE LOCATION AND FUNCTION OF THE DETECTION DEVICES,
 OPERATING DEVICES, AUXILIARY EQUIPMENT, AND ELECTRICAL
 CIRCUITRY, IF USED. APPARATUS AND DEVICES USED SHALL BE
 IDENTIFIED. ANY SPECIAL FEATURES SHALL BE ADEQUATELY
 EXPLAINED.
  
 5.1.2.3.1
 PRE-ENGINEERED SYSTEMS SHALL NOT BE REQUIRED TO SPECIFY
 AN INTERNAL VOLUME OF THE CONTAINER, NOZZLE FLOW RATES,
 EQUIVALENT LENGTHS OF PIPE, FITTINGS, AND HOSE, OR FLOW
 CALCULATIONS, WHEN USED WITHIN THEIR LISTED
 LIMITATIONS. THE INFORMATION REQUIRED BY THE LISTED
 SYSTEM DESIGN MANUAL, HOWEVER, SHALL BE MADE AVAILABLE
 TO THE AUTHORITY HAVING JURISDICTION FOR VERIFICATION
 THAT THE SYSTEM IS WITHIN ITS LISTED LIMITATIONS.
  
 5.1.2.4
 AN ?AS-BUILT? INSTRUCTION AND MAINTENANCE MANUAL THAT
 INCLUDES A FULL SEQUENCE OF OPERATIONS AND A FULL SET
 OF DRAWINGS AND CALCULATIONS SHALL BE MAINTAINED ON
 SITE.
  
 5.1.2.5 FLOW CALCULATIONS.
 5.1.2.5.1
 FLOW CALCULATIONS ALONG WITH THE WORKING PLANS SHALL BE
 SUBMITTED TO THE AUTHORITY HAVING JURISDICTION FOR
 APPROVAL. THE VERSION OF THE FLOW CALCULATION PROGRAM
 SHALL BE IDENTIFIED ON THE COMPUTER CALCULATION
 PRINTOUT.
  
 5.1.2.5.2
 WHERE FIELD CONDITIONS NECESSITATE ANY MATERIAL CHANGE
 FROM APPROVED PLANS, THE CHANGE SHALL BE SUBMITTED FOR
 APPROVAL.
  
 5.1.2.5.3
 WHEN SUCH MATERIAL CHANGES FROM APPROVED PLANS ARE
 MADE, CORRECTED ?AS-INSTALLED? PLANS SHALL BE PROVIDED.
  
 5.1.3 APPROVAL OF PLANS.
 5.1.3.1
 PLANS AND CALCULATIONS SHALL BE APPROVED PRIOR TO
 INSTALLATION.
  
 4) IS THIS BUILDING EQUIPPED WITH A COMPLETE AND FULLY
 FUNCTIONAL FIRE SPRINKLER SYSTEM? IF SO, PLEASE PROVIDE
 LAYOUT OF THE FIRE SPRINKLER SYSTEM IN RELATION TO THE
 CLEAN AGENT SYSTEM BEING INSTALLED.
  
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  
  
  
  