Plan Review Notes
Plan Review Notes For Permit 18040104
Permit Number 18040104
Review Stop B
Sequence Number 3
Notes
Date Text
2018-10-23 19:03:39****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC EC = FBC ENERGY CONSERVATION
  
 SEVERAL COMMENTS WERE NOT ADDRESSED. PRIOR TO CO OR
 TCO, SUBMIT A REVISION ADDRESSING THE FOLLOWING:
  
 1. FBC A 207, REVISE PLAN TO INDICATE WHICH METHOD OF
 COMPLIANCE IS ELECTED (ACCESSIBLE MEANS OF EGRESS,
 IBC2000 OR IBC2003).
  
 2. ALS.0.1, BUILDING TYPE IIA WITH A NOTE THAT PER
 TABLE 601 FOOTNOTE D, 1 HR FIRE RESISTANCE RATING
 SUBSTITUTED BY FIRE SPRINKLER. THIS CAN ONLY BE TAKEN
 IF THE SPRINKLERS ARE NOT REQUIRED BY OTHER PROVISIONS
 OF THE CODE. A STORY INCREASE WAS TAKEN (FROM 3 TO 4),
 SO THIS EXCEPTION CANNOT BE UTILIZED.
  
 RESPONSE LETTER STATES TO SEE ATTACHED LETTER. THIS WAS
 AGREED TO BY BUILDING OFFICIAL WITH RATIONALE TO BE
 PRESENTED IN A SIGNED AND SEALED LETTER, PLEASE
 PROVIDE.
  
 3. ALS.1.1, REGARDING THE EXISTING STAIR: FBC EB 805.2
 EXCEPTION 2, THIS WAS COMPLIANT UNDER THE CODE UNDER
 WHICH IT WAS CONSTRUCTED. INSPECTOR WILL VERIFY THAT
 DEVIATION BETWEEN STAIR TREADS WILL ADJUSTED IF UNSAFE.
 PER ARCHITECT, THE GUARDRAIL AND HANDRAIL WILL BE
 CONSTRUCTED TO COMPLY WITH FBC B 2014.
  
 4. A0.0.2, A WOOD CEILING IS SHOWN. IF THIS IS A TYPE I
 OR TYPE II BUILDING, THIS APPEARS TO BE PROHIBITED, SEE
 FBC B 603 FOR COMBUSTIBLES PERMITTED IN A NON
 COMBUSTIBLE BUILDING.
  
 RESPONSE LETTER STATES THAT SPEC SHEETS SHOWING
 COMPLIANCE ARE ATTACHED; UNABLE TO LOCATE.
  
 5. SEOR TO REVIEW SOILS; INCORPORATE REFERENCE INTO
 PLAN OR PROVIDE A SHOP DRAWING REVIEW STAMP.
  
 6. ENERGY CALCS, CLARIFY THE FOLLOWING OR REVISE
 ACCORDINGLY:
 A. EXTERNAL LIGHTING IS NONE; HOW WILL THIS BUILDING
 COMPLY WITH MEANS OF EGRESS ILLUMINATION IN THE EXIT
 DISCHARGE? SIGNAGE FOR THE BUILDING? LIGHTS ON THE
 EXTERIOR? SP1.0.1 SHOWS EXTERIOR LIGHTING.
 B. WALLS SHOWN FOR 2ND FLOOR ONLY, WHERE IS THE DATA
 FOR THE OTHERS?
 C. WINDOWS SHOWN ON 2ND FLOOR ONLY, WHERE IS DATA FOR
 THE OTHERS?
 D. NO DOORS SHOWN.
 E. NO DATA FOR ROOF; AREN'T THERE TWO DIFFERENT TYPES
 OF ROOFS ON THIS BUILDING?
 F. FLOORS APPEAR TO SHOW SLAB ON GRADE FOR ALL LEVELS.
  
 7. COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
 CONFIRM COMPLIANCE WITH PRESSURES SHOWN ON SHEET S0.0.5
 PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS OPTIONS,
 INDICATE OPTION PROPOSED, ESPECIALLY IF NOT ALL OPTIONS
 COMPLY WITH MINIMUM DESIGN PRESSURES. PRODUCTS TO BE
 SUBMITTED (LIST MAY NOT BE COMPREHENSIVE):
 NANAWALL
 STOREFRONT
 GLAZED DOORS
 OPAQUE DOORS
 OVERHEAD DOORS
  
 WHEN SUBMITTING PRODUCT APPROVALS, PROVIDE A LOCATION
 PLAN.
  
 8. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 ALL OTHER ITEMS OTHER THAN BMEP
  
  
 ***************************
 INTERNAL USE ONLY:
  
 USC-404 TYPE 437 - ALT: NON-RES, NON-HSKPG
 SQUARE FEET - 36706
  
 CONSTRUCTION TYPE: IIA
 UNITS:
 FLOORS: 4
 BEDROOMS:
 ROOMS:
 SQ FT LIVABLE: 36706
 SQ FT FOOTPRINT: 36706
 SQ FT ROOF: 36706
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD:
 PROP USE: OFFICE
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS:
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED B
  
  