| 2018-10-23 19:03:39 | ****PROVISOS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | SEVERAL COMMENTS WERE NOT ADDRESSED. PRIOR TO CO OR |
| | TCO, SUBMIT A REVISION ADDRESSING THE FOLLOWING: |
| | |
| | 1. FBC A 207, REVISE PLAN TO INDICATE WHICH METHOD OF |
| | COMPLIANCE IS ELECTED (ACCESSIBLE MEANS OF EGRESS, |
| | IBC2000 OR IBC2003). |
| | |
| | 2. ALS.0.1, BUILDING TYPE IIA WITH A NOTE THAT PER |
| | TABLE 601 FOOTNOTE D, 1 HR FIRE RESISTANCE RATING |
| | SUBSTITUTED BY FIRE SPRINKLER. THIS CAN ONLY BE TAKEN |
| | IF THE SPRINKLERS ARE NOT REQUIRED BY OTHER PROVISIONS |
| | OF THE CODE. A STORY INCREASE WAS TAKEN (FROM 3 TO 4), |
| | SO THIS EXCEPTION CANNOT BE UTILIZED. |
| | |
| | RESPONSE LETTER STATES TO SEE ATTACHED LETTER. THIS WAS |
| | AGREED TO BY BUILDING OFFICIAL WITH RATIONALE TO BE |
| | PRESENTED IN A SIGNED AND SEALED LETTER, PLEASE |
| | PROVIDE. |
| | |
| | 3. ALS.1.1, REGARDING THE EXISTING STAIR: FBC EB 805.2 |
| | EXCEPTION 2, THIS WAS COMPLIANT UNDER THE CODE UNDER |
| | WHICH IT WAS CONSTRUCTED. INSPECTOR WILL VERIFY THAT |
| | DEVIATION BETWEEN STAIR TREADS WILL ADJUSTED IF UNSAFE. |
| | PER ARCHITECT, THE GUARDRAIL AND HANDRAIL WILL BE |
| | CONSTRUCTED TO COMPLY WITH FBC B 2014. |
| | |
| | 4. A0.0.2, A WOOD CEILING IS SHOWN. IF THIS IS A TYPE I |
| | OR TYPE II BUILDING, THIS APPEARS TO BE PROHIBITED, SEE |
| | FBC B 603 FOR COMBUSTIBLES PERMITTED IN A NON |
| | COMBUSTIBLE BUILDING. |
| | |
| | RESPONSE LETTER STATES THAT SPEC SHEETS SHOWING |
| | COMPLIANCE ARE ATTACHED; UNABLE TO LOCATE. |
| | |
| | 5. SEOR TO REVIEW SOILS; INCORPORATE REFERENCE INTO |
| | PLAN OR PROVIDE A SHOP DRAWING REVIEW STAMP. |
| | |
| | 6. ENERGY CALCS, CLARIFY THE FOLLOWING OR REVISE |
| | ACCORDINGLY: |
| | A. EXTERNAL LIGHTING IS NONE; HOW WILL THIS BUILDING |
| | COMPLY WITH MEANS OF EGRESS ILLUMINATION IN THE EXIT |
| | DISCHARGE? SIGNAGE FOR THE BUILDING? LIGHTS ON THE |
| | EXTERIOR? SP1.0.1 SHOWS EXTERIOR LIGHTING. |
| | B. WALLS SHOWN FOR 2ND FLOOR ONLY, WHERE IS THE DATA |
| | FOR THE OTHERS? |
| | C. WINDOWS SHOWN ON 2ND FLOOR ONLY, WHERE IS DATA FOR |
| | THE OTHERS? |
| | D. NO DOORS SHOWN. |
| | E. NO DATA FOR ROOF; AREN'T THERE TWO DIFFERENT TYPES |
| | OF ROOFS ON THIS BUILDING? |
| | F. FLOORS APPEAR TO SHOW SLAB ON GRADE FOR ALL LEVELS. |
| | |
| | 7. COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY |
| | DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING |
| | DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION. |
| | CONFIRM COMPLIANCE WITH PRESSURES SHOWN ON SHEET S0.0.5 |
| | PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS OPTIONS, |
| | INDICATE OPTION PROPOSED, ESPECIALLY IF NOT ALL OPTIONS |
| | COMPLY WITH MINIMUM DESIGN PRESSURES. PRODUCTS TO BE |
| | SUBMITTED (LIST MAY NOT BE COMPREHENSIVE): |
| | NANAWALL |
| | STOREFRONT |
| | GLAZED DOORS |
| | OPAQUE DOORS |
| | OVERHEAD DOORS |
| | |
| | WHEN SUBMITTING PRODUCT APPROVALS, PROVIDE A LOCATION |
| | PLAN. |
| | |
| | 8. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE |
| | REQUIRED FOR: |
| | LIGHT POLES/SITE LIGHTING |
| | FIRE ALARM |
| | FIRE SPRINKLER |
| | LOW VOLTAGE |
| | ACCESS |
| | LANDSCAPING |
| | IRRIGATION |
| | ALL OTHER ITEMS OTHER THAN BMEP |
| | |
| | |
| | *************************** |
| | INTERNAL USE ONLY: |
| | |
| | USC-404 TYPE 437 - ALT: NON-RES, NON-HSKPG |
| | SQUARE FEET - 36706 |
| | |
| | CONSTRUCTION TYPE: IIA |
| | UNITS: |
| | FLOORS: 4 |
| | BEDROOMS: |
| | ROOMS: |
| | SQ FT LIVABLE: 36706 |
| | SQ FT FOOTPRINT: 36706 |
| | SQ FT ROOF: 36706 |
| | |
| | SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF |
| | KNOWN): |
| | SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN): |
| | XX.XX |
| | SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN: |
| | XX.XX |
| | OCC LOAD: |
| | PROP USE: OFFICE |
| | SPRINKLER SYS? Y |
| | SPRK REQ'D? Y |
| | BATHRMS: |
| | |
| | BLDG CODE: FL 2014 |
| | OCC CLASS: 5TH ED B |
| | |
| | |