| 2018-08-15 07:50:59 | 2ND REVIEW- PART 2, FBC-2017 MECHANICAL |
| | PERMIT #18040104 |
| | 8/21/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | THE FOLLOWING COMMENTS ARE BASED ON THE 1ST REVIEW |
| | COMMENTS WHICH STILL EXIST EITHER PARTIALLY OR |
| | COMPLETELY . |
| | |
| | 1) THE REQUESTED ELECTRONICALLY SIGNED AND SEALED |
| | ENERGY AND AC CALCULATIONS WERE NOT PROVIDED. |
| | |
| | 2) THE ENERGY COMPLIANCE FORM IS INDICATING THE VRF |
| | UNITS ARE "WATER SOURCE" BUT THAT DOES NOT MATCH WITH |
| | THE EQUIPMENT SCHEDULES PROVIDED ON THE PLANS WHICH |
| | INDICATE AIR SOURCE UNITS- SEE TABLE C403.2.3(11) FBC |
| | EC. |
| | |
| | 3) THE ENERGY COMPLIANCE FORM DOES NOT LIST ANY DATA |
| | FOR RTU-2 (528.2 MBH) AND THE OARTU (107.1 MBH) - |
| | PLEASE PROVIDE THE DATA. |
| | |
| | 4) M7.1 & M7.2: THE ENERGY COMPLIANCE FORM LISTS RTU-1 |
| | AS A 93.3 MBH UNIT, HOWEVER THERE IS NO RTU-1 IN THE |
| | SCHEDULES OR WITH THAT COOLING CAPACITY. |
| | |
| | 5) AS PREVIOUSLY NOTED IN THE FIRST REVIEW, THERE IS NO |
| | COMPLIANCE DATA LISTED IN THE ENERGY COMPLIANCE FORM |
| | FOR AHU'S 5, 6, 7, & 8. |
| | |
| | 6) REFER TO SHEETS M2.5, M6.1 AND M7.1: PLEASE CORRECT |
| | THE LABELING OF THE LARGE 528.2 MBH RTU WHICH IS |
| | INDICATED AS RTU-2 ON THE PLANS, AND RTU-1 IN THE |
| | SCHEDULE. |
| | |
| | 7) SHEETS ALS.01 AND M0.1 HAVE NOT BEEN UPDATED TO LIST |
| | THE CORRECT CODE EDITIONS AND THE CORRECT NOA # FOR THE |
| | ROOF STAND. |
| | |
| | 8) SHEET M6.1: PLEASE PROVIDE EXHAUST VENTILATION |
| | CALCULATIONS AND AIR BALANCE CALCULATIONS ON THE PLAN. |
| | |
| | 9) SHEET M2.1: PLEASE CLARIFY HOW O/A IS BEING PROVIDED |
| | TO THE LOUNGE ROOM THAT IS CLOSE TO THE STAIRCASE, AND |
| | HOW MAKEUP AIR IS BEING PROVIDED FOR THE TOILET ROOM |
| | EXHAUST SYSTEM. |
| | |
| | 10) SHEET M2.2: REFER TO SECTION 502.13 FBC M AND |
| | CLARIFY HOW THE EXHAUST VENTILATION SYSTEM IN THE |
| | GARAGE WILL OPERATE- CONTINOUSLY OR IN ACCORDANCE WITH |
| | SECTION 404. PLEASE PROVIDE EXHAUST VENTILATION |
| | CALCULATIONS FOR THE GARAGE. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |
| | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18040104 |
| | 8/15/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) 2ND REQUEST FOR ELECTRONICALLY SIGNED AND SEALED |
| | ENERGY AND AC CALCULATIONS- SEE COMMENT #1 FROM THE 1ST |
| | REVIEW. |
| | |
| | 2) ACCORDING TO THE RESPONSE NARRATIVE TO THE 1ST |
| | REVIEW COMMENTS, SHEETS M0.1, M2.1, M2.5, M6.1, AND |
| | M7.1 HAVE BEEN REVISED, HOWEVER THOSE SHEETS HAVE NOT |
| | BEEN UPDATED, AND M6.1 HAS BEEN REPLACED WITH E.01. THE |
| | REVIEW IS STOPPED AT THIS POINT UNITL REVISED SHEETS |
| | ARE UPLOADED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |