| Plan Review Notes For Permit 18040104 |
| Permit Number |
18040104 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-07-24 14:01:30 | PERMIT # 18040104 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | 2ND REVIEW COMMENTS: | | | | | | 1) BECAUSE THIS BUILDING DOES NOT HAVE AN EXISTING FIRE | | | SPRINKLER SYSTEM AND/OR FIRE ALARM SYSTEM: ENGINEERED | | | FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION DOCUMENTS | | | ARE REQUIRED FOR A GENERAL/MASTERL BUILDING PERMIT. | | | AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE | | | SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS | | | (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS) | | | FOR A SUB-PERMIT. | | | | | | 2) PER FLORIDA ADMINISTRATIVE CODE SECTION | | | 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS | | | SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER | | | SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE | | | TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR | | | EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN | | | DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT | | | FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION | | | SUCH AS PRE-ENGINEERED SYSTEMS. | | | | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4751 | | | |
|