| Date |
Text |
| 2018-06-05 07:37:19 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 553.79(5) 2016, THIS IS A THRESHOLD BUILDING (FOUR |
| | STORIES). |
| | ***NO WORK TO RESUME ON THE STRUCTURE PERMIT UNTIL THE |
| | FOLLOWING ITEMS ARE ADDRESSED*** |
| | FAILURE TO IMMEDIATELY RESOLVE THESE ISSUES WILL RESULT |
| | IN REVOCATION OF THE STRUCTURE PERMIT 17120610 AS THIS |
| | PERMIT WAS ISSUED IN ERROR. |
| | |
| | 1. COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT |
| | OF UNDERSTANDING; THIS HAS BEEN SENT VIA EMAIL TO |
| | CONTRACTOR. |
| | |
| | 2. PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL |
| | PROPOSED INSPECTORS. |
| | |
| | 3. THRESHOLD STATEMENT REQUIRED BY FS553.79(7)(D) - |
| | ENGINEER, REVISE THE STATEMENT SO IT IS CLEAR THAT IT |
| | IS FOR COMPLIANCE WITH THE STATUTORY REQUIREMENT. |
| | SUGGESTED: |
| | |
| | "PER FS553.79, TO THE BEST OF THE ENGINEER'S KNOWLEDGE, |
| | THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | MINIMUM BUILDING CODES AND THE APPLICABLE FIRESAFETY |
| | STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS CHAPTER AND CHAPTER 633." |
| | |
| | PER BUILDING OFFICIAL - ALL STRUCTURAL PAGES FOR THE |
| | STRUCTURE PERMIT 17120610 ARE TO BE REVISED TO INCLUDE |
| | THE STATUTORY STATEMENT. |
| | |
| | 4. THRESHOLD INSPECTION PLAN REQUIRED BY FS553.79(5)A); |
| | S0.03, PLEASE REVISE TITLE OF THIS PAGE SO IT IS CLEAR |
| | THAT THIS SERVES AS A THRESHOLD INSPECTION PLAN. |
| | |
| | |
| | |
| | |