2018-05-02 11:46:48PERMIT # 18040104
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) SHEET ALS 1.0: THE TRAVEL DISTANCE TO THE STAIRS BY
 THE PRODUCTION ROOM (003) INDICATES 270 FEET. PER NFPA
 101, CHAPTER 39, TRAVEL DISTANCE MAY NOT EXCEED 200
 FEET IF THE BUILDING IS NOT PROTECTED BY A FIRE
 SPRINKLER SYSTEM. PLEASE PROVIDE FOR CODE COMPLIANCE OR
 JUSTIFICATION.
  
 39.2.6.2
 TRAVEL DISTANCE TO AN EXIT SHALL NOT EXCEED 200 FT (61
 M) FROM ANY POINT IN A BUILDING, UNLESS OTHERWISE
 PERMITTED BY 39.2.6.3.
  
 39.2.6.3
 TRAVEL DISTANCE SHALL NOT EXCEED 300 FT (91 M) IN
 BUSINESS OCCUPANCIES PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 9.7.
  
 2) SHEET ALS 1.1: INDICATES AN EGRESS TRAVEL DISTANCE
 OF 202 FEET. PLEASE PROVIDE FOR COMPLIANCE OF CODE, AS
 NOTED ABOVE, OR JUSTIFICATION.
  
 3) SHEET ALS 1.4: PLEASE PROVIDE JUSTIFICATION THAT
 SHOWS COMPLIANCE WITH ALL APPLICABLE ASPECTS OF NFPA
 101: 7.2.12 - AREA OF REFUGE; INCLUDING ALL DIMENSIONS
 APPLICABLE TO THE STAIRWELL (MIN CLEAR WIDTH OF 48
 INCHES IS REQUIRED - - STAIR A HAS A CLEAR WIDTH OF
 ONLY 44 INCHES), LOCATION OF REQUIRED SIGNAGE, TWO-WAY
 COMMUNICATION (IF REQUIRED), ETC.
  
 4) PER NFPA 101: 39.3.4 - A FIRE ALARM SYSTEM IS
 REQUIRED FOR THIS OCCUPANCY.
  
 5) DOES THIS BUILDING HAVE A FULL OR PARTIAL FIRE
 SPRINKLER SYSTEM? OR IS A FIRE SPINKLER SYSTEM GOING TO
 BE INSTALLED?
  
 6) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 7) COULD NOT FIND DETAILS FOR STAIR A. NOT INCLUDED IN
 SHEETS A6-0-1 THROUGH A6-0-5.
  
 8) ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 DURING PLAN RESUBMISSION.
  
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  