| Date |
Text |
| 2018-05-21 09:43:02 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. ELECTRICAL RISER NOTE 7 SHOWS A WIREWAY FOR FUTURE |
| | TENANTS. THIS WIREWAY SHOULD BE TIED INTO THE GROUNDING |
| | ELECTRODE SYSTEM. PROVIDE CORRECTION. NEC 250.50, |
| | 250.58 |
| | 2. ELECTRICAL RISER NOTE 7 SHOWS A WIREWAY FOR FUTURE |
| | TENANTS. THE WIREWAY IS SHOWN AS BEING INSTALLED, WHILE |
| | THE METERS AND DISCONNECTS ARE SHOWN AS FUTURE. THIS |
| | WIREWAY CANNOT BE INSTALLED WITH ENERGIZED CONDUCTORS |
| | AND NO OVERCURRENT PROTECTION. PROVIDE CORRECTION. NEC |
| | 230.70 |
| | 3. PROVIDE LABELING OF MAINS PER NEC 230.2(E) |
| | 4. THE NEC AND FBC SPECIFIED FOR DESIGN ON SHEET |
| | ALS.0.1 AND E0.1 IS NOT THE CURRENT CODE. PROVIDE |
| | CORRECTION. FBC PREFACE (ALSO SEE CURRENT CODES ABOVE) |
| | 5. SHEET ALS.0.1 INDICATES THAT THE BUILDING IS FULLY |
| | SPRINKLERED. IS THERE A FIRE PUMP AND CONTROLLER, OR IS |
| | THIS FED FROM CITY WATER? PLEASE CLARIFY. WPB FBC |
| | 107.2.1 |
| | 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 7. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 8. RESTROOMS ON 3RD FLOOR DO NOT SHOW THE AUTOMATIC |
| | LIGHTING CONTROL REQUIRED. PROVIDE CORRECTION. FBC EC |
| | C405.2 |
| | 9. SHEET E2.5, THE UNISEX RESTROOM DOES NOT SHOW THE |
| | AUTOMATIC LIGHTING CONTROL REQUIRED. PROVIDE |
| | CORRECTION. FBC EC C405.2 |
| | 10. PROVIDE NOTE REQUIRING GFCI DEVICE FOR WATER |
| | COOLERS TO BE READILY ACCESSIBLE. NEC 422.5 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |