Plan Review Notes
Plan Review Notes For Permit 18040104
Permit Number 18040104
Review Stop B
Sequence Number 1
Notes
Date Text
2018-06-09 15:51:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. SP1.0.1 AREA FOR THE ROOF TERRACE OPEN TO AIR (4685
 SF) IS NOT CONSISTENT WITH THE ROOF PLAN WHICH SHOWS
 1845 SF, REVISE OR CLARIFY, FBC B 1004.
  
 2. SP1.0.1 PARKING IS SHOWN AS 48 SPACES AND 1 HANDICAP
 SPACE. FBC A TABLE 208.2, TWO ACCESSIBLE SPACES ARE
 REQUIRED.
  
 3. SP1.0.1 FBC B TABLE 705.8, REVISE PLAN TO SHOW
 COMPLIANCE. DISTANCE TO CENTER OF ROAD IS NOT CLEAR
 (ALLEY).
  
 4. FBC A 207, REVISE PLAN TO INDICATE WHICH METHOD OF
 COMPLIANCE IS ELECTED (ACCESSIBLE MEANS OF EGRESS,
 IBC2000 OR IBC2003).
  
 5. ALS.0.1, CHANGE OF OCCUPANCY IS NOTED FOR THE 4TH
 FLOOR. THE AREAS WHICH WERE ENCLOSED BUT NOT
 CONDITIONED ARE ALSO CHANGE OF OCCUPANCY. THE
 CONVERSION OF EXTERIOR SPACE UNDER ROOF TO INTERIOR
 SPACE IS AN ADDITION. REVISE CODE SUMMARY TO CLARIFY
 SCOPE OF WORK.
  
 6. ALS.0.1, COMPLIANCE WITH FBC B TABLE 503 NOT CLEAR.
 SHEET ALS 0.1 STATES THAT THIS IS NON SEPARATED MIXED
 USE "BUSINESS: 9000 SF/STORY X 3 = 27,000 SF/FLOOR".
  
 SEE FBC B 508.3.2, COMPLIANCE WITH THE MOST STRINGENT
 OCCUPANCY IS TO BE SHOWN; IN THIS CASE ASSEMBLY. 9000
 SF IS THE LIMITATION FOR BUSINESS, TYPE V CONSTRUCTION
 WHICH WITH SPRINKLER INCREASE IS LIMITED TO 3 STORIES.
 REVISE PLAN TO INCLUDE BUILDING TYPE AND SHOW
 COMPLIANCE WITH FBC B TABLE 503.
  
 7. ALS.0.1, FBC 107, REVISE PLAN TO INCLUDE BUILDING
 TYPE, OR ADVISE WHERE THIS INFORMATION CAN BE FOUND.
  
 8. ALS.0.1, "SMOKE EVACUATION REQUIREMENT", NFPA101 IS
 REFERENCED. REVISE TO INCLUDE FBC. PROVIDE A SECTION SO
 EXCEPTION TO SMOKE CONTROL IS CLEAR, FBC B 404.5.
  
 9. FBC 107.3.5.1.1(5), FBC EB 904, PROVIDE FIRE
 PROTECTION PLANS TO SHOW COMPLIANCE WITH STANDPIPES FBC
 B 905.3.1(1) AND NFPA13 SPRINKLERS FBC B 903.2.11.3.
  
 10. FBC 107.3.5.1.1(6), FBC EB 904, PROVIDE FIRE ALARM
 PLANS TO SHOW COMPLIANCE WITH FBC B 907.2.2.
  
 11. ALS.1.1, FBC 107, NOTE STATES THAT "2014 FBC
 SECTION 1004.4 FIXED SEATING" (CONFERENCE ROOM), IS
 THIS CORRECT? IF THIS IS NOT FIXED SEATING, REVISE NOTE
 AND REVISE OCCUPANT LOAD ACCORDINGLY.
  
 12. ALS.1.1, PLAN INDICATES SIGNAGE AT STAIR INDICATING
 NO ACCESS. IT DOES NOT APPEAR THAT A SIGN WILL BE
 ADEQUATE TO PREVENT USE OF THE STAIR. ADDITIONAL MEANS
 MAY BE REQUIRED. PRIOR TO C.O. ADDITIONAL INFORMATION
 WILL BE REQUIRED REGARDING HOW OCCUPANTS WILL BE
 PREVENTED FROM ACCESSING THE STAIR. UNLESS YOU WISH TO
 REVISE THE PLAN OR PROPOSE SOMETHING AT THIS TIME, THIS
 WILL BE A PROVISO ITEM.
  
 OR, SEE FBC EB 805.2 EXCEPTION 2.
  
 13. COVER SHEET, FBC B 501.2, ADDRESS IDENTIFICATION,
 IS THE ADDRESS SHOWN CONCEPTUAL, OR INTENDED TO COMPLY
 WITH THIS SECTION?
  
 14. ALS.1.2, FBC A 202.4, IT APPEARS THAT A PORTION OF
 THE 2ND FLOOR LACKS VERTICAL ACCESSIBILITY. PROVIDE
 RATIONALE. PLEASE PROVIDE VIA EMAIL PRIOR TO
 RESUBMITTAL.
  
 15. AD.1.2.3, FBC 107, CLARIFY EXISTING OCCUPANCY OF
 THE ROOFTOP ROOM.
  
 16. ALS1.4, FBC B 1021.1, IT APPEARS THAT THE ROOF
 TERRACE IS REQUIRED TO HAVE TWO MEANS OF EGRESS. IS THE
 DOTTED LINE A DOOR IN THE NANAWALL? DOES IT HAVE
 HARDWARE? NOTE STATES "HOLD OPEN ON STATIONARY DOOR".
 IT'S NOT CLEAR HOW THIS COMPLIES WITH FBC B 1008.1.10,
 PANIC BARS.
  
 17. A0.0.2, A WOOD CEILING IS SHOWN. IF THIS IS A TYPE
 I OR TYPE II BUILDING, THIS APPEARS TO BE PROHIBITED,
 SEE FBC B 603 FOR COMBUSTIBLES PERMITTED IN A NON
 COMBUSTIBLE BUILDING.
  
 18. PLUMBING ACCESSIBILITY COMMENTS ARE APPLICABLE FOR
 BUILDING REVIEW.
  
 19. SEE THRESHOLD REVIEW. ALL STRUCTURAL SHEETS ARE TO
 INCLUDE THE STATEMENT REQUIRED BY FLORIDA STATUTE 553.
 A THRESHOLD INSPECTION PLAN IS REQUIRED AND THE PLAN IS
 TO BE NOTED AS SUCH. PLANS FOR THE STRUCTURE PERMIT AND
 FOR THIS INTERIOR PERMIT ARE TO BE REVISED.
  
 20. A.8.0.1, FBC B TABLE 716.5, THE DOORS IN THE TWO
 HOUR STAIR EXIT ENCLOSURES ARE REQUIRED TO BE 90
 MINUTE. FOR EXAMPLE, DOOR 210 SHOWS NO RATING, 216
 PROPOSES 45 MINUTE; REVISE AND CHECK ALL.
  
 21. A.8.0.1, NO PANIC HARDWARE PROPOSED ON ROOF
 TERRACE; ALL DOORS SERVING ASSEMBLY OCCUPANCY AND AN
 OCCUPANT LOAD 50 AND OVER ARE TO HAVE PANIC BARS FBC B
 1008.1.10.
  
 22. SEOR TO REVIEW SOILS; INCORPORATE REFERENCE INTO
 PLAN OR PROVIDE A SHOP DRAWING REVIEW STAMP.
  
 23. THE STRUCTURE PERMIT WAS ISSUED TO QUEST
 CONTRACTING. THIS APPLICATION WAS SUBMITTED BY DPR
 CONSTRUCTION. WILL THE CONTRACTOR BE CHANGED TO QUEST?
 IF NOT, PRIOR TO ISSUANCE OF THIS PERMIT A LETTER
 SIGNED BY THE QUALIFIERS OF THE TWO COMPANIES STATING
 THAT THEY WILL WORK TOGETHER TO OBTAIN CODE COMPLIANCE,
 FBC 107. THIS IS REQUIRED WHEN THERE IS MORE THAN ONE
 CONTRACTOR ON A PROJECT AND RESPONSIBILITIES MAY
 OVERLAP.
  
 24. FBC B 3306, IT APPEARS THAT A BARRIER AND OVERHEAD
 PROTECTION ARE REQUIRED. ACQUIRE PERMITS. IT APPEARS
 THAT WORK HAS ALREADY BEEN DONE WITHOUT THIS PROTECTION
 IN PLACE.
  
 25. ENERGY CALCS, CLARIFY THE FOLLOWING OR REVISE
 ACCORDINGLY:
 A. EXTERNAL LIGHTING IS NONE; HOW WILL THIS BUILDING
 COMPLY WITH MEANS OF EGRESS ILLUMINATION IN THE EXIT
 DISCHARGE? SIGNAGE FOR THE BUILDING? LIGHTS ON THE
 EXTERIOR? SP1.0.1 SHOWS EXTERIOR LIGHTING.
 B. WALLS SHOWN FOR 2ND FLOOR ONLY, WHERE IS THE DATA
 FOR THE OTHERS?
 C. WINDOWS SHOWN ON 2ND FLOOR ONLY, WHERE IS DATA FOR
 THE OTHERS?
 D. NO DOORS SHOWN.
 E. NO DATA FOR ROOF; AREN'T THERE TWO DIFFERENT TYPES
 OF ROOFS ON THIS BUILDING?
 F. FLOORS APPEAR TO SHOW SLAB ON GRADE FOR ALL LEVELS.
  
 26. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING
 PROVISOS:
  
 A. COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
 CONFIRM COMPLIANCE WITH PRESSURES SHOWN ON SHEET S0.0.5
 PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS OPTIONS,
 INDICATE OPTION PROPOSED, ESPECIALLY IF NOT ALL OPTIONS
 COMPLY WITH MINIMUM DESIGN PRESSURES. PRODUCTS TO BE
 SUBMITTED (LIST MAY NOT BE COMPREHENSIVE):
 NANAWALL
 STOREFRONT
 GLAZED DOORS
 OPAQUE DOORS
 OVERHEAD DOORS
  
 WHEN SUBMITTING PRODUCT APPROVALS, PROVIDE A LOCATION
 PLAN.
  
 C. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 ALL OTHER ITEMS OTHER THAN BMEP
  
  
 ***************************
 INTERNAL USE ONLY:
  
 USC-404 TYPE 437 - ALT: NON-RES, NON-HSKPG
 SQUARE FEET - 36706
  
 CONSTRUCTION TYPE: ???
 UNITS:
 FLOORS: 4
 BEDROOMS:
 ROOMS:
 SQ FT LIVABLE: 36706
 SQ FT FOOTPRINT: 36706
 SQ FT ROOF: 36706
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD:
 PROP USE: OFFICE
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS:
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED B
  
  