| 2019-09-17 09:05:58 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | BE ADVISED, BECAUSE A NEW ELECTRICAL PLAN WAS SUBMITTED |
| | BY AN ENGINEER, THIS REVIEW IS NEW AND PREVIOUS |
| | COMMENTS ARE DISCARDED. |
| | |
| | 1. PER THE WPB AMENDMENTS TO THE FBC: SUBMITTAL |
| | DOCUMENTS CONSISTING OF CONSTRUCTION DOCUMENTS, |
| | STATEMENT OF SPECIAL INSPECTIONS, GEOTECHNICAL REPORT |
| | AND OTHER DATA SHALL BE SUBMITTED IN TWO OR MORE SETS |
| | WITH EACH PERMIT APPLICATION. NOTICE THE WORD "SETS". |
| | THE SUBMISSION PROVIDED IS VERY DISORGANIZED AND NOT IN |
| | TWO COMPLETE SETS. PROVIDE CORRECTION. WPB FBC 107.1 |
| | 2. A BLOCK NOTE ON SHEET E-1 STATES THAT OTHER SHEETS |
| | WERE PROVIDED AND PREVIOUSLY APPROVED FOR THE |
| | ELECTRICAL IN THE ROOMS. THIS IS NOT CORRECT. THE |
| | ENGINEER OF RECORD SHOULD SUPPLY PLANS FOR ALL THE WORK |
| | TO BE COMPLETED DESCRIBED IN THE SCOPE OF WORK. TO |
| | DATE, THERE ARE NO APPROVED PLANS FOR ANY PORTION OF |
| | THE ELECTRICAL WORK. PER THE WPB AMENDMENTS TO THE FBC: |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| | FOR SPECIFIC INFORMATION. PROVIDE CORRECTIONS. WPB FBC |
| | 107.2.1 |
| | 3. PROVIDE ACCURATE LOAD CALCULATION FOR THE SERVICE. |
| | THE ENGINEER HAS USED THE DEMAND LOAD FROM EACH PANEL, |
| | AND THEN FURTHER APPLIED A DEMAND FACTOR TO THIS NUMBER |
| | BASED ON THE TABLE IN NEC 220.84. THIS VIOLATES HOW |
| | THIS CODE ARTICLE SHOUOLD BE APPLIED. PROVIDE |
| | CORRECTION. NEC 220.84(C) |
| | 4. IN REFERENCE TO LAD CALCULATION, THE RISER DIAGRAM |
| | SHOW 13 METERS, AND 13 RUNS TO UNITS, BUT THE LOAD |
| | CALCULATION ONLY INCLUDES 12 UNITS. STUDIO IS NOT SHOWN |
| | ON PLANS. CORRECT DISCREPANCIES, PROVIDE CORRECTION. |
| | NEC 215.2, 220; WPB FBC 107.2.1 |
| | 5. IN REFERENCE TO LAD CALCULATION, PANEL SCHEDULE |
| | SHOWS ONLY ONE SMALL APPLIANCE CIRCUIT. A MINIMUM OF |
| | TWO 20 AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO |
| | SUPPLY KITCHEN COUNTERTOP RECEPTACLE OUTLET(S). PROVIDE |
| | CORRECTION. NEC 210.11(C)(1) |
| | 6. RISER DIAGRAM SHOWS THREE RUNS OF 500 KCMIL WIRE FOR |
| | THE SERVICE DROP. PER NEC 240.4(C), THE AMPACITY OF THE |
| | CONDUCTORS FEEDING THIS OVERCURRENT DEVICE SHALL BE |
| | RATED EQUAL TO OR GREATER THAN THE OVERCURRENT DEVICE. |
| | PROVIDE CORRECTION. NEC 240.4(C) |
| | 7. AFCI PROTECTION SHOWN IN NOTE 2 OF PANEL HAS NOT |
| | BEEN APPLIED PROPERLY TO THE CIRCUITS THAT REQUIRE AFCI |
| | PROTECTION. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| | KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| | RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| | SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS |
| | INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES. |
| | SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION. |
| | PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902; |
| | FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE. |
| | 8. AS THE PLAN PROVIDED IS MISSING A SUBSTANTIAL AMOUNT |
| | OF INFORMATION, A FULL REVIEW IS NOT POSSIBLE AT THIS |
| | TIME. FURTHER REVIEW COMMENTS MAY BE POSSIBLE WHEN |
| | CORRECTIONS ARE SUBMITTED. WPB FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |