| 2019-04-22 15:44:57 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | NOTICE COMMENT 16 BELOW. THIS PLAN IS NOT ACCEPTABLE AS |
| | IS. THE CAPACITY OF THE SERVICE EXCEEDS THE AMOUNT |
| | PERMITTED TO BE DESIGNED BY AN ELECTRICAL CONTRACTOR. |
| | ADDITIONALLY, FURTHER INFORMATION SUBMITTED WAS |
| | SUBMITTED ON 8.5 X 11 PAPER. THE WEST PALM BEACH |
| | AMMENDMENTS TO THE FBC REQUIRE A MINIMUM OF 1/8 SCALE |
| | PLAN. A LICENSED DESIGN PROFESSIONAL SHOULD PROVIDE |
| | CORRECTIONS AS NOTED BELOW. WPB FBC 107.2.1.3 |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. CORRECTED. |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. DUE TO ADJUSTMENT OF VALUE, ADDITIONAL FEES FOR PLAN |
| | REVIEW ARE DUE PRIOR TO THE NEXT PLAN REVIEW CYCLE. WPB |
| | FBC 105.1 (ADDITIONAL FEES NOT PAID, A HOLD WILL BE |
| | PLACED ON PERMIT UNTIL FEES ARE PAID.) |
| | |
| | NEW COMMENTS: |
| | |
| | 7. RISER DIAGRAM PROVIDED SHOWS WHAT APPEARS TO BE A |
| | 1200 AMP METER BANK. WILL THIS HAVE A 1200 AMP BREAKER |
| | AS A MAIN DISCONNECT SO AS NOT TO EXCEED THE MAXIMUM |
| | NUMBER OF MAINS PERMITTED? THIS IS NOT EXPLAINED ON |
| | RISER DIAGRAM. IF SO, PROVIDE ARC ENERGY REDUCTION PER |
| | NEC 240.87. PROVIDE DETAILS. WPB FBC 107.2.1; NEC |
| | 230.71 |
| | 8. RISER SHOWS PARALLEL 600 KCMIL COPPER AS SERVICE |
| | CONDUCTORS. THE AMPACITY OF TWO RUNS OF 600 KCMIL |
| | COPPER IS 840 AMPS. PER CODE, THE AMPACITY OF THESE |
| | CONDUCTORS SHALL BE EQUAL TO OR GREATER THAN THE |
| | OVERCURRENT DEVICE. PROVIDE CORRECTION. NEC 240.4(C) |
| | 9. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION |
| | INCLUDING INFORMATION FROM THE POWER COMPANY STATING |
| | WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE |
| | SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE |
| | EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9, |
| | 110.10 |
| | 10. PANEL SCHEDULE PROVIDED SOES NOT SHOW THE GFCI |
| | PROTECTED RECEPTACLE OUTLET ON A 20 AMP CIRCUIT THAT IS |
| | REQUIRED WITHIN 3 FEET OF EACH BASIN. PROVIDE |
| | CORRECTION. NEC 210.11(C)(3), 210.52(D) |
| | 11. PROVIDE LOAD CALCULATION FOR EACH PANEL AND FOR |
| | SERVICE TO CONFIRM THAT THE SERVICE IS ADEQUATELY |
| | SIZED. NEC 220; WPB FBC 107.2.1 |
| | 12. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| | PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1 |
| | 13. RISER SHOWS A 1/0 COPPER GROUNDING ELECTRODE |
| | CONDUCTOR. THE GROUNDING ELECTRODE CONDUCTOR SHOULD BE |
| | SIZED FOR THE TOTAL AREA OF THE SERVICE CONDUCTORS. |
| | SHOW ALL AVAILABLE GROUNDING ELECTRODES. PROVIDE |
| | CORRECTION. NEC 250.50, 250.66 |
| | 14. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. |
| | FBC EC C405.1, R404.1 |
| | 15. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12 |
| | 16. DESIGN OF ELECTRICAL SYSTEM IS SHOWN AS 1200 AMP. |
| | THIS IS NOT PERMITTED TO BE DESIGNED BY THE ELECTRICAL |
| | CONTRACTOR PER FLORIDA STATUTES. PROVIDE PLAN BY A |
| | DESIGN PROFESSIONAL. FS 471.003(2)(H); WPB FBC 107.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |