| Date |
Text |
| 2018-08-31 13:53:26 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND |
| | SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE |
| | ELECTRICAL CONTRACTOR QUALIFIER. PER WPB FBC 107.2.1.3, |
| | BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH |
| | SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE |
| | MEDIUM. PROVIDE CORRECTION. FS 471.003(2)(H); 471.025; |
| | WPB FBC 107.2.1, 107.3.5 (NOT PROVIDED) |
| | 2. CORRECTED. |
| | 3. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY |
| | SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| | 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, |
| | E3609.3; WPB FBC 107.2.1 (NOT PROVIDED.) |
| | 4. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING ANY |
| | NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR |
| | THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE |
| | APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12, |
| | 215.5, 408.4; WPB FBC 107.3.5 (NOT PROVIDED.) |
| | 5. WORK DESCRIPTION STATES THAT ALL ELECTRICAL OUTLETS |
| | AND SWITCHES WILL BE REPLACED. PROVIDE AFCI AND/OR GFCI |
| | PROTECTION TO MEET CODE. NEC 406.4(D)(3 AND 4) (NOT |
| | PROVIDED.) |
| | |
| | NEW COMMENT: |
| | |
| | 6. DUE TO ADJUSTMENT OF VALUE, ADDITIONAL FEES FOR PLAN |
| | REVIEW ARE DUE PRIOR TO THE NEXT PLAN REVIEW CYCLE. WPB |
| | FBC 105.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |