| 2018-04-06 12:19:02 | PERMIT # 18040097 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | APPROVED WITH COMMENTS: |
| | |
| | 1) ALL WORK AND REQUIREMENTS SHALL COMPLY WITH THE 6TH |
| | EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH |
| | CONTAINS THE 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 |
| | WITH FLORIDA AMENDMENTS. |
| | |
| | 2) PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND |
| | DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF |
| | NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| | REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| | PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| | OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| | |
| | 3) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION |
| | SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND |
| | RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION |
| | SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A |
| | 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A |
| | FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED |
| | BY EMAIL ([email protected]) OR IN WRITING (FAX: |
| | 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE |
| | MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.? |
| | |
| | 4) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER |
| | SYSTEM AND/OR FIRE ALARM SYSTEM. |
| | |
| | |