2018-05-07 13:04:31PASS PROVISO
 1) REFER TO SECTION C403.2.4.3 SHUTOFF DAMPERS
 AUTOMATIC DAMPERS REQUIRED FOR FRESH AIR.
 2017 FLORIDA ENERGY CODE
 2) REFER TO SECTION 301.15 2017 FBC (M)
 WIND RESISTANCE. PROVIDE ENGINEER DETAIL
 ON CURB TIEDOWN TO ROOF AND RTU TIEDOWN
 TO CURB. DETAIL PROVIDED WITH THE PLAN ARE
 NOT COMPLETE.
 3) REFER TO SECTION 606.3 INSTALLATION. DUCT DETECTORS
 2017 FBC (M)
  