| 2018-05-07 13:04:31 | PASS PROVISO | | | 1) REFER TO SECTION C403.2.4.3 SHUTOFF DAMPERS | | | AUTOMATIC DAMPERS REQUIRED FOR FRESH AIR. | | | 2017 FLORIDA ENERGY CODE | | | 2) REFER TO SECTION 301.15 2017 FBC (M) | | | WIND RESISTANCE. PROVIDE ENGINEER DETAIL | | | ON CURB TIEDOWN TO ROOF AND RTU TIEDOWN | | | TO CURB. DETAIL PROVIDED WITH THE PLAN ARE | | | NOT COMPLETE. | | | 3) REFER TO SECTION 606.3 INSTALLATION. DUCT DETECTORS | | | 2017 FBC (M) | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-808-6732 | | | FAX 561-805-6676 |
|