Plan Review Notes
Plan Review Notes For Permit 18040095
Permit Number 18040095
Review Stop E
Sequence Number 1
Notes
Date Text
2018-05-06 13:09:54CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. IN PANEL SCHEDULE FOR MDPB THERE IS A LOAD SHOWN FOR
 CTB. PANEL SCHEDULE FOR CTB SHOWS NO LOADS. PROVIDE
 CLARIFICATION AND/OR CORRECTION. FBC 107.2.1
 2. IN THE TRANSFORMER SCHEDULE, TCTB AND TXR SHOW A
 SECONDARY BREAKER AT 150 AMP WITH A FEEDER OF SIZE # 1.
 THIS WIRE SIZE IS NOT RATED FOR 150 AMPS. PROVIDE
 CORRECTION. NEC 310.15(B)(16)
 3. DESIGNATE ON PLAN WHICH AREAS ARE PATIENT CARE
 SPACES THAT WILL HAVE WIRING INSTALLED PER NEC 517.13.
 4. PANELS SHOWN WITH AN ISOLATED GROUND DO NOT SHOW THE
 ISOLATED GROUNDING CONDUCTOR INCLUDED IN THE CONDUIT.
 PROVIDE CORRECTION. WPB FBC 107.2.1; NEC 250.96(B)
 5. ISOLATED GROUND RECEPTACLES ARE SHOWN IN
 MAMMOGRAPHY, BONE DENSITY, AND ULTRASOUND AREAS.
 SECTION 517.16 OF THE NEC STATES THAT ISOLATED GROUND
 RECEPTACLES SHALL NOT BE INSTALLED WITHIN A PATIENT
 CARE VICINITY. PROVIDE CORRECTION. NEC 517.16
 6. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
 7. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE IN CHILLER AREA. NEC 210.63
 8. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER
 CODE. NEC 210.64
 9. ARE THERE ANY WINDOW DISPLAYS THAT WOULD REQUIRE A
 SHOW WINDOW OUTLET? NEC 210.62
 10. PANEL SCHEDULE FOR PANEL F IS MISSING INFORMATION.
 PROVIDE COMPLETE PANEL SCHEDULE. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  