| 2018-05-06 13:09:54 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. IN PANEL SCHEDULE FOR MDPB THERE IS A LOAD SHOWN FOR |
| | CTB. PANEL SCHEDULE FOR CTB SHOWS NO LOADS. PROVIDE |
| | CLARIFICATION AND/OR CORRECTION. FBC 107.2.1 |
| | 2. IN THE TRANSFORMER SCHEDULE, TCTB AND TXR SHOW A |
| | SECONDARY BREAKER AT 150 AMP WITH A FEEDER OF SIZE # 1. |
| | THIS WIRE SIZE IS NOT RATED FOR 150 AMPS. PROVIDE |
| | CORRECTION. NEC 310.15(B)(16) |
| | 3. DESIGNATE ON PLAN WHICH AREAS ARE PATIENT CARE |
| | SPACES THAT WILL HAVE WIRING INSTALLED PER NEC 517.13. |
| | 4. PANELS SHOWN WITH AN ISOLATED GROUND DO NOT SHOW THE |
| | ISOLATED GROUNDING CONDUCTOR INCLUDED IN THE CONDUIT. |
| | PROVIDE CORRECTION. WPB FBC 107.2.1; NEC 250.96(B) |
| | 5. ISOLATED GROUND RECEPTACLES ARE SHOWN IN |
| | MAMMOGRAPHY, BONE DENSITY, AND ULTRASOUND AREAS. |
| | SECTION 517.16 OF THE NEC STATES THAT ISOLATED GROUND |
| | RECEPTACLES SHALL NOT BE INSTALLED WITHIN A PATIENT |
| | CARE VICINITY. PROVIDE CORRECTION. NEC 517.16 |
| | 6. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| | SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND |
| | SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN |
| | THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE |
| | INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN |
| | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC |
| | 105.1, 107.2.1 |
| | 7. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C |
| | EQUIPMENT PER CODE IN CHILLER AREA. NEC 210.63 |
| | 8. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER |
| | CODE. NEC 210.64 |
| | 9. ARE THERE ANY WINDOW DISPLAYS THAT WOULD REQUIRE A |
| | SHOW WINDOW OUTLET? NEC 210.62 |
| | 10. PANEL SCHEDULE FOR PANEL F IS MISSING INFORMATION. |
| | PROVIDE COMPLETE PANEL SCHEDULE. WPB FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |