2018-05-23 10:10:07BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PROJECT IS FOR SELECTIVE DEMOLITION, ADDITION AND
 INTERIOR BUILDOUT OF AN EXISTING BUILDING.
 TYPE OF CONSTRUCTION IS II B
 OCCUPANCY CLSSIFICATION IS B -BUSINESS
  
 1. PALM BEACH COUNTY IMPACT FEES MAY BE REQUIRED FOR
 THE 562 SQ. FT. ADDITION.
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
 2. ROOFING PERMIT REQUIRED.
 PROVIDE PRODUCT APPROVALS FOR PROPOSED ROOFING SYSTEM
 COMPONENTS OR DESIGNER MAY CHOOSE TO DEFER THESE
 SUBMITTALS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 3. PROVIDE ABOVE CEILING IDENTIFICATION FOR THE 2 HR
 FIRE WALL C1 PER FBC 703.7.
 703.7 MARKING AND IDENTIFICATION.
 WHERE THERE IS AN ACCESSIBLE CONCEALED FLOOR,
 FLOOR-CEILING OR ATTIC SPACE, FIRE WALLS, FIRE
 BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS AND SMOKE
 PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE PROTECTED
 OPENINGS OR PENETRATIONS SHALL BE EFFECTIVELY AND
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING IN THE
 CONCEALED SPACE. SUCH IDENTIFICATION SHALL:
 1.BE LOCATED WITHIN 15 FEET (4572 MM) OF THE END OF
 EACH WALL AND AT INTERVALS NOT EXCEEDING 30 FEET (9144
 MM) MEASURED HORIZONTALLY ALONG THE WALL OR PARTITION.
 2. INCLUDE LETTERING NOT LESS THAN 3 INCHES (76 MM) IN
 HEIGHT WITH A MINIMUM 3/8-INCH (9.5 MM) STROKE IN A
 CONTRASTING COLOR INCORPORATING THE SUGGESTED WORDING,
 ?FIRE AND/OR SMOKE BARRIER?PROTECT ALL OPENINGS,? OR
 OTHER WORDING.
  
 4. PROVIDE SOILS REPORT FOR ADDITION PER FBC 1803.
 1803.1 GENERAL.
 GEOTECHNICAL INVESTIGATIONS SHALL BE CONDUCTED IN
 ACCORDANCE WITH SECTION 1803.2 AND REPORTED IN
 ACCORDANCE WITH SECTION 1803.6. WHERE REQUIRED BY THE
 BUILDING OFFICIAL OR WHERE GEOTECHNICAL INVESTIGATIONS
 INVOLVE IN-SITU TESTING, LABORATORY TESTING OR
 ENGINEERING CALCULATIONS, SUCH INVESTIGATIONS SHALL BE
 CONDUCTED BY A REGISTERED DESIGN PROFESSIONAL.
 1803.2 INVESTIGATIONS REQUIRED.
 GEOTECHNICAL INVESTIGATIONS SHALL BE CONDUCTED IN
 ACCORDANCE WITH SECTIONS 1803.3 THROUGH 1803.5.
  
 5. PROVIDE PHYSICIST REPORT FOR THE INSTALLATION OF
 LEAD LINED WALLS AND GLAZING.
  
 6. EGRESS SEE PLAN PAGE A120 GENERAL NOTES FOR THE
 FOLLOWING-
 6A. COMMON PATH OF TRAVEL SHALL BE PER FBC CHPT. 10
 SEC. 1006 TABLE 1006.2.1 UNSPRINKLED.
 6B. EXIT ACCESS TRAVEL DISTANCE SHALL BE PER FBC CHPT.
 10 SEC. 1017 TABLE 1017.2 UNSPRINKLED.
 6C. TRAVEL DISTANCE AND COMMON PATH OF TRAVEL DISTANCES
 ARE NOT IDENTIFIED ON EXIT PATHS. SEE NOTES 6A AND 6B
 ABOVE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  
  
  
  
  
  