| Plan Review Notes For Permit 18040058 |
| Permit Number |
18040058 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-05-31 16:05:21 | 05/31/2018 2ND PLUMBING REVIEW**DENIED** | | | | | | COMMENTS NOT ANSWERED FROM 1ST REVIEW | | | | | | 1) TOTAL JOB VALVE SEEMS LOW. PER WPB AMEND 109.3 | | | PROVIDE A SIGN BONA FIDE CONTRACT. | | | | | | 2) PROVIDE A DETAIL ON WHERE THE AUTO FILL CONNECTION | | | WILL BE MADE AND LOCATION OF THE BACKFLOW. ALSO A | | | SEPERATE PERMIT FOR THE ISOLATION BACK IS REQUIRED AND | | | CITY ORD #2853-95 ALSO REQUIRES A RPZ AT THE METER | | | WHICH YOU CAN DO BOTH BACKFLOWS ON 1 PERMIT. | | | | | | NEW COMMENTS: | | | | | | 1) SHT. S-1 REFERS TO AIR TEST OF PVC PIPING. PLASTIC | | | PIPING IS NOT APPROVED TO BE TESTED BY MEANS OF AIR. | | | FBC P 312.1 | | | | | | 2) SHT. 2 SAYS POOL PIPING IS NOT SUBJECT TO THE FBC | | | PLUMBING 2017 AND TO SEE BOAF INTERPRETATION. I WAS NOT | | | ABLE TO LOCATE ANY INTERPRETATION JUST A QUESTION | | | REGRADING THE USE OF FLEX PVC. REMOVE ENTIRE COMMENT. | | | FBC 107.2.1 | | | | | | 3) SHT .2 SAYS CONTRACTOR MAY PLUMB THE POOL IN ANY | | | OTHER WAY TO IMPROVE EFFICIENCY. NO CHANGE FROM THE | | | APPROVED PLAN ARE PERMITTED IN THE FIELD WITH OUT A | | | REVISION. REMOVE ENTIRE COMMENT. FBC 107.2.1 | | | | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|