Plan Review Notes
Plan Review Notes For Permit 18040058
Permit Number 18040058
Review Stop P
Sequence Number 1
Notes
Date Text
2018-04-12 07:47:5004/12/2018 1ST PLUMBING REVIEW**DENIED**
  
 1) TOTAL JOB VALVE SEEMS LOW. PER WPB AMEND 109.3
 PROVIDE A SIGN BONA FIDE CONTRACT.
  
 2) PROVIDE A DETAIL ON WHERE THE AUTO FILL CONNECTION
 WILL BE MADE AND LOCATION OF THE BACKFLOW. ALSO A
 SEPERATE PERMIT FOR THE ISOLATION BACK IS REQUIRED AND
 CITY ORD #2853-95 ALSO REQUIRES A RPZ AT THE METER
 WHICH YOU CAN DO BOTH BACKFLOWS ON 1 PERMIT.
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  