| Date |
Text |
| 2018-04-03 15:29:55 | 04/03/2018 1ST GAS REVIEW**DENIED** |
| | |
| | 1) PER F.A.C RULE-61G1-16.001 COPIES OF SIGNATURE AND |
| | SEAL ARE NOT PERMITTED AND MUST BE WET |
| | |
| | 2) VALUE OF JOB SEEMS LOW. PROVIDE A SIGNED BONA FIDE |
| | CONTRACT. 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE |
| | OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION |
| | OF |
| | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE |
| | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| | DENIED, UNLESS THE APPLICANT CAN SHOW |
| | DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED |
| | CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE |
| | APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL |
| | BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING |
| | ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE |
| | LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION |
| | COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), |
| | AS PUBLISHED BY INTERNATIONAL CODE CONGRESS. |
| | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE |
| | BUILDING OFFICIAL. |
| | |
| | 3) AS YOU ARE CHANGING THE LOCATION OF THE 2ND STAGE |
| | REGUALTOR AND THE TANK PROVIDE A ISOMETRIC DRAWING TO |
| | INCLUDE THE CUT SECTION OF PIPING FROM THE NEW L.P TANK |
| | TO THE BUILDING INLET. FBC 107.3.5 |
| | |
| | 4) PLEASE PROVIDE 2 COPIES OF ALL PAPERWORK. YOU HAVE |
| | INCLUDED ONLY 1 SET OF GAS REGUALTOR MANUFACTURE |
| | INSTALLATION MANUAL. FBC 107.3.5 |
| | |
| | TIM HUNT |
| | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |
| | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | 561-805-6695 |
| | [email protected] |
| | |