| Plan Review Notes For Permit 18040024 |
| Permit Number |
18040024 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-06-07 07:57:24 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 400.8 USES NOT PERMITTED | | | | | | UNLESS SPECIFICALLY PERMITTED IN 400.7, FLEXIBLE CORDS | | | AND CABLES | | | SHALL NOT BE USED FOR THE FOLLOWING: | | | | | | (1) AS A SUBSTITUTE FOR THE FIXED WIRING OF A | | | STRUCTURE. | | | | | | SUBMIT CUT SHEETS ON THE ELECTRICAL EQUIPMENT SHOWING | | | THE LISTING. 110.3 |
|