| Plan Review Notes For Permit 18040023 |
| Permit Number |
18040023 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-04-06 12:56:54 | PERMIT # 18040023 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | 1) FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING | | | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A | | | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN | | | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE | | | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST | | | BE SUBMITTED BY EMAIL ([email protected])AND APPROVED | | | BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT 500 NORTH | | | DIXIE HIGHWAY. | | | | | | 2) ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A | | | LOCK/UNLOCK INDICATOR. | | | | | | 3) PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN | | | STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE | | | MAINTAINED AT ALL TIMES. | | | | | | 4) SEPERATES PERMITS REQUIRED FOR ALL WORK DONE RELATED | | | TO THE FIRE ALARM AND SPRINKLER SYSTEM. | | | | | | 5) WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT | | | SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED | | | AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE | | | MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM | | | SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD | | | INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY | | | BE NEEDED. | | | | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | [email protected] | | | |
|