| Date |
Text |
| 2019-01-10 15:20:41 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES, NOTED FOR |
| | THIRD REVIEW. ANY NEW COMMENTS WILL BE LISTED AFTER |
| | PREVIOUS COMMENTS. |
| | |
| | THESE IS A SUBSTANTIAL AMOUNT OF INFORMATION ON THE |
| | SUBMITTED PLANS THAT IS NOT TO CODE. PLEASE BE ADVISED |
| | THAT SOME OF THESE COMMENTS HAVE NOT BEEN ADDRESSED FOR |
| | TWO REVIEWS. IF UPON THE NEXT REVIEW, IF IT IS |
| | NECESSARY TO REJECT THE SUBMITTED PLAN AGAIN FOR THE |
| | SAME REASONS, AN ADDITIONAL PLAN REVIEW IS REQUIRED. |
| | FLORIDA STATUTES STATE: WITH RESPECT TO EVALUATION OF |
| | DESIGN PROFESSIONALS DOCUMENTS, IF A LOCAL GOVERNMENT |
| | FINDS IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH |
| | THE FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT |
| | DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE |
| | TIMES FOR FAILURE TO CORRECT A CODE VIOLATION |
| | SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION, |
| | INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION, |
| | STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING, |
| | VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS |
| | SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF |
| | THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO |
| | CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH |
| | TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED |
| | FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT |
| | OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS |
| | REVIEW. FS 553.80(2)(B) THE ADDITIONAL FEE FOR THIS |
| | PROJECT WOULD BE $550.00. THIS IS BASED ON CURRENT |
| | PERMIT VALUE SHOWN OF $25,000.00 |
| | |
| | 1. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING ANY |
| | NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR |
| | THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE |
| | APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12, |
| | 210.19, 215.2, 215.5, 310.15(B)(16), 408.4; WPB FBC |
| | 107.3.5 (ELECTRICAL SERVICES ARE EITHER 120/208 VOLT 3 |
| | PHASE, OR 120/240 VOLT 3 PHASE (WHICH HAS A HIGH LEG). |
| | INDICATION ON PLAN IS THAT THE SERVICE IS 230 VOLT 3 |
| | PHASE, BUT THERE ARE LOADS SHOWN ON B PHASE WHICH WOULD |
| | BE THE HIGH LEG. PROVIDE CLARIFICATION AND CORRECTIONS |
| | AS NEEDED TO ACCURATELY REFLECT THE INSTALLATION.)(3RD |
| | REVIEW: PANEL SCHEDULES ARE STILL SHOWING THE WRONG |
| | VOLTAGE. PANEL A IS SHOWN BEING FED FROM B PHASE OF |
| | PANEL B, WHICH WOULD CREATE A HIGH LEG ON PANEL A AND |
| | PANEL A1, WHICH SHOW LOADS THAT SHOULD NOT BE CONNECTED |
| | TO A HIGH LEG.) |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. CORRECTED. |
| | 7. CORRECTED. |
| | 8. CORRECTED. |
| | 9. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS |
| | STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2 (3RD |
| | REVIEW, NOT PROVIDED. THIS IS A CHANGE OF OCCUPANCY, |
| | AUTOMATIC LIGHTING CONTROL IS REQUIRED.) |
| | 10. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. NEC 215.2, 220, 408.30 (NOT PROVIDED.)(3RD |
| | REVIEW: LOAD CALCULATION NOT CORRECT. AS EXPLAINED IN |
| | MEETING WITH EOR, A 50% DEMAND FACTOR FOR RECEPTACLE |
| | LOAD OVER 10,000 VA IS NOT PERMITTED AS SHOWN. ANY |
| | EQUIPMENT FED FROM AN OUTLET MUST BE CALCULATED AT 100% |
| | FOR NON-CONTINUOUS LOAD AND 125% FOR A CONTINUOUS LOAD. |
| | NEC 215.2, 220.14(A). ADDITIONALLY, THERE ARE LOADS |
| | SHOWN IN LOAD CALCULATION THAT ARE NOT SHOWN ANYWHERE |
| | ELSE ON PLAN. PROVIDE CORRECTIONS.) |
| | 11. CORRECTED. |
| | 12. CORRECTED. |
| | 13. CORRECTED. |
| | |
| | NEW COMMENTS: |
| | |
| | 14. CORDS ARE NOT TO BE USED IN LIEU OF PERMANENT |
| | WIRING METHODS, EXCEPT AS PERMITTED PER CODE. |
| | BREWMATION CONTROL DIAGRAM SHOWS CORDS GOING TO ALL OF |
| | THE EQUIPMENT FED FROM THIS CONTROL STATION. PROVIDE |
| | CLARIFICATION AND /OR CORRECTIONS. NEC 110.3, 400.7, |
| | 400.8 |
| | 15. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS |
| | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC |
| | 109.3 |
| | 16. RISER DIAGRAM SHOWS PARALLEL 4/0 WIRE FEEDING METER |
| | CAN AND PANEL B. THIS WIRE IS UNDERSIZED FOR THE LOAD |
| | SHOWN. THIS ALSO CONFLICTS WITH WHAT IS SHOWN IN PANEL |
| | SCHEDULE. PROVIDE CORRECTION. NEC 310.15(B)(16) |
| | 17. GROUNDING ELECTRODE CONNECTIONS ARE SHOWN IN RISER |
| | DIAGRAM AT METER CAN AND AT PANEL B. THE GROUNDING |
| | ELECTRODE SYSTEM IS TIED TO THE SERVICE IN ONE LOCATION |
| | ONLY. GROUNDING ELECTRODE CONDUCTORS SHOULD NOT BE |
| | INSTALLED TO PANEL B. PROVIDE CORRECTION. NEC 250.6, |
| | 250.24 |
| | 18. SERVICE RISER FROM METER CAN TO FPL SERVICE SHOULD |
| | NOT INCLUDE AN EQUIPMENT GROUNDING CONDUCTOR. PROVIDE |
| | CORRECTION. NEC 250.6, 250.24, 250.121 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |